| Plan Review Notes For Permit 19060202 |
| Permit Number |
19060202 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-21 15:02:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 301, SEE PAGE 11, ANCHOR NOTE 3, A 2.5" EDGE | | | DISTANCE IS REQUIRED, 2" PROPOSED ON THE INSTALLATION | | | SCHEDULE, REVISE. | | | | | | 2. AN 8' SPAN CANNOT USE A 12" SPACING FOR A C4 | | | CONNECTION, SEE CHART ON PAGE 11. | | | | | | 3. TO RESUBMIT, YOU MAY RESUBMIT UP TO TWO PAGES WITH A | | | RESUBMITTAL FORM VIA EMAIL TO [email protected]. THE | | | SUBJECT LINE MUST INCLUDE THE PERMIT NUMBER AND THE | | | WORD "RESUBMITTAL". | | | | | | | | | | | | |
|