Plan Review Notes
Plan Review Notes For Permit 19060192
Permit Number 19060192
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-27 10:25:531) SUBMIT A SANITARY RISER AND CORRESPONDING WATER
 RISER DIAGRAM FOR REVIEW. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 2) THE PLAN VIEW OF THE UNDERGROUND PLUMBING APPEARS TO
 SHOW FLAT, DRY VENTS. VENTS SHALL CONNECT TO A
 HORIZONTAL DRAIN ABOVE THE CENTERLINE OF THE HORIZONTAL
 DRAIN PIPE. 2017 FBC-PLUMBING SEC.905.3.
 3) THE PLAN VIEW SHOWS A SINK AND ICEMAKER DISCHARGING
 INTO A HORIZONTAL WET VENT. ONLY FIXTURES IN A BATHROOM
 GROUP SHALL DISCHARGE INTO THE WET VENT. 2017
 FBC-PLUMBING SEC.912.1.
 4) NOT MORE THAN ONE WET VENTED FIXTURE DRAIN SHALL
 DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN
 CONNECTION. 2017 FBC-PLUMBING SEC.912.2.1.
 5) THE NUMBER OF THE TYPE OF FIXTURES PERMITTED TO BE
 WET VENTED HAS BEEN EXCEEDED. REFER TO THE DEFINITION
 OF "BATHROOM GROUP" IN CHAPTER 2 OF THE 2017
 FBC-PLUMBING.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  