| Plan Review Notes For Permit 19060192 |
| Permit Number |
19060192 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-27 10:25:53 | 1) SUBMIT A SANITARY RISER AND CORRESPONDING WATER | | | RISER DIAGRAM FOR REVIEW. WPB AMEND. TO FBC SEC. | | | 107.3.5.1.3. | | | 2) THE PLAN VIEW OF THE UNDERGROUND PLUMBING APPEARS TO | | | SHOW FLAT, DRY VENTS. VENTS SHALL CONNECT TO A | | | HORIZONTAL DRAIN ABOVE THE CENTERLINE OF THE HORIZONTAL | | | DRAIN PIPE. 2017 FBC-PLUMBING SEC.905.3. | | | 3) THE PLAN VIEW SHOWS A SINK AND ICEMAKER DISCHARGING | | | INTO A HORIZONTAL WET VENT. ONLY FIXTURES IN A BATHROOM | | | GROUP SHALL DISCHARGE INTO THE WET VENT. 2017 | | | FBC-PLUMBING SEC.912.1. | | | 4) NOT MORE THAN ONE WET VENTED FIXTURE DRAIN SHALL | | | DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN | | | CONNECTION. 2017 FBC-PLUMBING SEC.912.2.1. | | | 5) THE NUMBER OF THE TYPE OF FIXTURES PERMITTED TO BE | | | WET VENTED HAS BEEN EXCEEDED. REFER TO THE DEFINITION | | | OF "BATHROOM GROUP" IN CHAPTER 2 OF THE 2017 | | | FBC-PLUMBING. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|