Plan Review Notes
Plan Review Notes For Permit 19060106
Permit Number 19060106
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-06 13:01:58JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 FAIL
  
 CLARIFY FLOORING MATERIALS AND PROVIDE TEST REPORTS
 THAT DEMONSTRATE COMPLIANCE WITH THE SECTIONS BELOW;
  
 FBC 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED
 FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE
 W/FLAME SPREAD INDEX OF 200 OR LESS.
  
 FBC 804 ? FLOORING
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  