| 2019-06-06 13:01:58 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) | | | 805-6724 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | FAIL | | | | | | CLARIFY FLOORING MATERIALS AND PROVIDE TEST REPORTS | | | THAT DEMONSTRATE COMPLIANCE WITH THE SECTIONS BELOW; | | | | | | FBC 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED | | | FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE | | | W/FLAME SPREAD INDEX OF 200 OR LESS. | | | | | | FBC 804 ? FLOORING | | | | | | FBC 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E | | | | | | 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | |
|