| 2019-07-17 11:14:45 | 2ND REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED | | | | | | | | | 1) PROVIDE 2 COPIES WITH NARRATIVE OF THE SCOPE OF WORK | | | BEING DONE. YOU PLAN IS TOO BASIC AND THE FIELD | | | INSPECTOR'S MAY NOT BE CLEAR ON THE SCOPE OF WORK. TO | | | BE CLEAR THE ONLY WORK IS THE GUEST BATH TUB TO SHOWER, | | | NEW MASTER TUB, AND KITCHEN ISLAND. NO OTHER FIXTURES | | | OR TILE IS BEING REPLACED? FBC 107.3.5 | | | THERE WAS ONLY 1 SET OF OF PLANS WITH THE SCOPE OF WORK | | | PLEASE SUBMIT SECOND COPY. PER WPB AMEND TO FBC 107.1 | | | | | | 2) PROVIDE SHOWER PAN DETAIL TO INCLUDE THE TOTAL | | | OFFSET OF THE DRAIN, PAN MATERIAL BEING USED, | | | PRE-PITCHING OF FLOOR @ 2%MIN, AND A COMPLETE FIRE | | | STOPPING DETAIL. FBC 107.3.5 | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|