Plan Review Notes
Plan Review Notes For Permit 19060057
Permit Number 19060057
Review Stop P
Sequence Number 1
Notes
Date Text
2019-07-03 11:19:53INTERACTIVE WATER FEATURE REVIEW
  
 1) THE SPECIFIC ADDRESS OF THE WATER FEATURE SHALL BE
 PLACED ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SUCTION
 DRAIN COVERS. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. XF 102 REFERS TO A CIVIL SHEET FOR THE LOCATION
 OF THE WASTE LINE. THERE IS NO CIVIL DRAWING IN THIS
 SUBMITTAL. CLARIFY. SUBMIT A CIVIL DRAWING SHOWING THE
 TERMINATION LOCATION OF THE WASTE LINE. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) THE PLANS ARE REQUIRED TO BE APPROVED BY CITY PLACE
 RETAIL LLC. THE PLANS CAN BE STAMPED BY THEM OR A
 LETTER OF APPROVAL FROM THEM IS REQUIRED. SEE ZONING
 COMMENTS.
 SUBMIT A COPY OF THE PALM BEACH COUNTY HEALTH
 DEPARTMENT FORM DH 4159 THAT IS REQUIRED FOR
 CONSTRUCTION OF THE INTERACTIVE WATER FEATURE. FL.
 STATUTE 514.025.
 5) THE DIGITAL SIGNATURE OF THE PROFESSIONAL ENGINEER
 CAN NOT BE SELF CERTIFIED PER THE BOARD OF FLORIDA
 ENGINEER'S.
 6) SHOP DRAWING SUBMITTALS, AS NOTED IN THE
 SPECIFICATION BOOK, ARE REQUIRED TO BE REVIEWED BY THE
 DESIGNER OF RECORD OF THE PROJECT AND MARKED WITH THEIR
 SHOP DRAWING REVIEW STAMP PRIOR TO SUBMITTAL TO THE
 BUILDING DEPARTMENT FOR REVIEW. FBC 107.3.4.1 DEFERRED
 SUBMITTALS.
 7) THE DISCHARGE LOCATION/TERMINATION OF THE WASTE LINE
 SHALL RECEIVE APPROVAL FROM THE CITY OF WEST PALM BEACH
 ENGINEERING DEPT. CONTACT MANNY GONZALEZ AT
 561-494-1085.
 8) THE MINIMUM SIZE OF THE COLLECTOR TANK SHALL BE
 EQUAL TO THE VOLUME OF 3 MINUTES OF THE COMBINED FLOW
 OF ALL FEATURE PUMPS AND THE FILTER PUMP PER 2017
 FBC-BUILDING SEC. 454.1.9.8. SUBMIT VERIFICATION OF
 COMPLIANT DESIGN CAPACITY OF THE COLLECTOR TANK.
 9) THE FLOW RATE THROUGH THE FEATURE NOZZLES OF THE
 WATER FEATURES SHALL BE SUCH AS NOT TO HARM THE PATRONS
 AND SHALL NOT EXCEED 20 FEET PER SECOND UNLESS
 JUSTIFIED BY THE DESIGN ENGINEER AND BY THE FOUNTAIN
 MANUFACTURER PERR 2017 FBC SEC. 454.1.9.8.6.4. SUBMIT
 VERIFICATION.
 10) ADEQUATE ACCESS SHALL BE PROVIDED TO THE COLLECTOR
 TANK. 2017 FBC SEC. 454.1.9.8.
 11) A MEANS OF VACUUMING AND COMPLETELY DRAINING THE
 COLLECTOR TANK SHALL BE PROVIDED PER 2017 FBC
 SEC.454.1.9.8.6.7.
 12) SHT.XM 140 - KEYNOTE 10.404 IS SHOWN IN THE SUCTION
 LINE FROM THE RESERVOIR TO THE FILTER TANKS BUT IS NOT
 LISTED IN THE KEYNOTE SCHEDULE. CLARIFY & IDENTIFY THE
 PART. WPB AMEND. TO FBC. SEC. 107.2.1.
 13) SHT. XM 140 - CLARIFY THE LETTERS W/AR ON THE
 OVERFLOW LINE & P/AR ON THE POTABLE WATER LINE. PB
 AMEND. TO FBC SEC. 107.2.1.
 14) SHT. XD 100 - PROVIDE THE SCHEDULE KEYNOTE FOR ITEM
 13.054 ON DETAIL 6.
 15) SUBMIT MSDS DOCUMENTS FOR THE CHEMICALS TO BE USED/
 STORED ON SITE AND THE QUANTITIES OF EACH.WPB AMEND. TO
 FBC SEC. 107.2.1.
 16) SUBMIT MANUF. SPECIFICATIONS ON THE DRENCH SHOWER.
 17) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DECK
 SHOWER. THE DECK SHOW SHALL COMPLY WITH THE 2017
 FBC-ACCESSIBILITY SECS.305 (CLEAR FLOOR SPACE), 402.1
 (ACCESSIBLE ROUTE), 308 (REACH RANGES) & 309 (OPERABLE
 PARTS).
 18) SHT. XD 101 - DETAIL #1 - SHOW THE LOCATION OF THE
 STORAGE PIT ON THE DRAWINGS. WPB AMEND. TO FBC SEC.
 107.2.1.
 19) ALL PIPING SHALL BE TESTED AT 35 PSI.
 20) SUBMIT SPECIFICATIONS AND SHOW THE LOCATION OF THE
 DRENCH SHOWER AS REFERENCED IN THE JOB SPECIFICATIONS.
 21)THE MAXIMUM ALLOWABLE QUANTITIES OF THE CHLORINE AND
 MURIATIC ACID SHALL COMPLY WITH 2017 FBC SEC.307.1 AND
 TABLES 307.1 (1) AND 307.1 (2).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  