Plan Review Notes
Plan Review Notes For Permit 19060057
Permit Number 19060057
Review Stop M
Sequence Number 1
Notes
Date Text
2019-07-03 16:46:001ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19060057
 7/3/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET XM100: VENTILATION REQUIREMENTS FOR THE
 CHEMICAL ROOM AND FILTRATION FEATURE ROOM ARE LISTED
 UNDER UTILITY DATA, HOWEVER NO SYSTEMS OR DETAILS ARE
 PROVIDED ON THE PLANS- SEE SECTION 107.2.1 WPB AND
 PROVIDE DRAWINGS AND SPECIFICATIONS.
  
 2) REFER TO SECTION 414.1.3 FBC B- INFORMATION
 REQUIRED:
 "A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY."
 PLEASE PROVIDE THE REQUIRED INFORMATION ON THE PLAN IN
 THE FORM OF A SCHEDULE LISTING EACH MATERIAL, THE
 QUANTITY OF THE MATERIAL, AND WHERE THE MATERIAL IS TO
 BE USED OR STORED. SUBMIT MSDS SHEETS FOR ALL
 MATERIALS.
  
 3) PLEASE NOTE THAT ROOMS AND SPACES ENCLOSING
 HAZARDOUS MATERIALS SHALL BE IDENTIFIED AS CONTROL
 AREAS AND ARE REQUIRED TO BE SEPARATED FROM OTHER ROOMS
 OR CONTROL AREAS BY FIRE BARRIERS AND HORIZONTAL
 ASSEMBLIES- SEE SECTIONS 414.2.1 & 414.2.2 FBC B AND
 REVISE THE PLANS ACCORDINGLY.
  
 4) HAZARDOUS EXHAUST SYSTEMS SHALL COMPLY WITH SECTIONS
 510.2- 510.10 FBC M. THE CURRENT PLANS DO NOT PROVIDE
 ANY EXHAUST VENTILATION DETAILS. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719