| 2019-07-03 16:46:00 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19060057 |
| | 7/3/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET XM100: VENTILATION REQUIREMENTS FOR THE |
| | CHEMICAL ROOM AND FILTRATION FEATURE ROOM ARE LISTED |
| | UNDER UTILITY DATA, HOWEVER NO SYSTEMS OR DETAILS ARE |
| | PROVIDED ON THE PLANS- SEE SECTION 107.2.1 WPB AND |
| | PROVIDE DRAWINGS AND SPECIFICATIONS. |
| | |
| | 2) REFER TO SECTION 414.1.3 FBC B- INFORMATION |
| | REQUIRED: |
| | "A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL |
| | IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF |
| | HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED |
| | SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO |
| | SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION |
| | CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE |
| | METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT |
| | NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS |
| | AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE |
| | REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION |
| | AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON, |
| | FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL |
| | AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY." |
| | PLEASE PROVIDE THE REQUIRED INFORMATION ON THE PLAN IN |
| | THE FORM OF A SCHEDULE LISTING EACH MATERIAL, THE |
| | QUANTITY OF THE MATERIAL, AND WHERE THE MATERIAL IS TO |
| | BE USED OR STORED. SUBMIT MSDS SHEETS FOR ALL |
| | MATERIALS. |
| | |
| | 3) PLEASE NOTE THAT ROOMS AND SPACES ENCLOSING |
| | HAZARDOUS MATERIALS SHALL BE IDENTIFIED AS CONTROL |
| | AREAS AND ARE REQUIRED TO BE SEPARATED FROM OTHER ROOMS |
| | OR CONTROL AREAS BY FIRE BARRIERS AND HORIZONTAL |
| | ASSEMBLIES- SEE SECTIONS 414.2.1 & 414.2.2 FBC B AND |
| | REVISE THE PLANS ACCORDINGLY. |
| | |
| | 4) HAZARDOUS EXHAUST SYSTEMS SHALL COMPLY WITH SECTIONS |
| | 510.2- 510.10 FBC M. THE CURRENT PLANS DO NOT PROVIDE |
| | ANY EXHAUST VENTILATION DETAILS. PROVIDE COMPLETE |
| | DETAILS AND SPECIFICATIONS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |