| 2020-03-24 14:15:54 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHEETS E-1 AND E-3 APPEAR TO BE IDENTICAL. WHY ARE |
| | THERE TWO IDENTICAL SHEETS IN THE SET? PROVIDE |
| | CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1 |
| | 2. LOAD CALCULATION SHOWS THE LOAD ON A PHASE AND C |
| | PHASE TO BE GREATER THAN 300 AMPS. THE GENERATOR IS |
| | SHOWN WITH A 300 AMP BREAKER. HOW WILL THIS HANDLE THE |
| | LOAD? PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC |
| | 110.3, 702.4(B)(2) |
| | 3. TOTAL COMPUTED LOAD FOR EACH PHASE IS NOT ACCURATE. |
| | FOR PHASES A AND C, THE LOAD WOULD BE DIVIDED BY 120 |
| | VOLTS. FOR B PHASE, THE LOAD WOULD BE DIVIDED BY 208 |
| | VOLTS. PROVIDE ACCURATE LOAD CALCULATION. NEC 220; WPB |
| | FBC 107.2.1 |
| | 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 5. PROVIDE NOTES FOR REQUIRED MARKING OF HIGH LEG. NEC |
| | 110.15, 230.56, 408.3(E) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |