| 2020-01-27 05:54:40 | 1) 3RD REQUEST - THE PLANS INDICATE AN EXISTING GAS |
| | METER AND CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR |
| | THIS ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM |
| | MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO |
| | ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF |
| | UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| | 402.2, 402.3. |
| | NOTE:I PUT A COPY OF THE ORIGINAL GAS PLAN IN THE |
| | PERMIT APPLICATION PACKAGE AFTER THE LAST REVIEW TO BE |
| | GIVEN TO THE CONTRACTOR TO USE AS A REFERENCE FOR THE |
| | EXISTING GAS LOAD. PLEASE USE THIS DRAWING TO COMPLY |
| | WITH THE PLAN REVIEW COMMENTS. |
| | 2)THE ORIGINAL GAS PLAN ON FILE IN CITY RECORDS SHOW A |
| | DEVELOPED LENGTH OF 158 FEET BUT THE SUBMITTED PLAN |
| | SHOWS A DEVELOPED LENGTH OF 20 FEET. CLARIFY. THE 158 |
| | SHALL BE USED TO SIZE THIS SYSTEM. 2017 FBC-FUEL GAS |
| | SEC. 402.4. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |