| Plan Review Notes For Permit 19060025 |
| Permit Number |
19060025 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-12-11 05:25:42 | 1) INDICATE ON THE PLAN THE TYPE OF PIPING TO BE USED | | | ABOVEGROUND AND SHOW THE REQUIRED LISTED GAS SHUTOFF | | | VALVE FOR THE GENERATOR.. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) A UNION IS REWUIRED WITHIN ONE FOOT UPSTREAM OR | | | DOWNSTREAM OF THE REGULATOR. 2017 FBC-FUEL GAS SEC. | | | 410.2 (7) . | | | 3) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD | | | OF THE REGULATOR. 2017 FBC-FUEL GAS SEC.409.4. | | | 4) - -2ND REQUEST - THE PLANS INDICATE AN EXISTING GAS | | | METER AND CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR | | | THIS ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM | | | MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO | | | ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF | | | UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO | | | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING | | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN | | | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO | | | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE | | | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, | | | 402.2, 402.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|