| 2019-06-27 13:27:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) IT APPEARS THAT THE FUEL SUPPY IS NATURAL GAS. |
| | |
| | THERE ARE NO NATURAL GAS LINS INDICATED. A SEPARATE |
| | PERMIT IS REQUIRED FOR THE NATURAL GAS LINES INCULDING |
| | EQUIPEMT SPECIFICATIONS. |
| | |
| | PLEASE SHOW THE PROPOSED NATURAL GAS LINES ON THE SITE |
| | PLAN AND PROVIDE A NOTE STATING UNDER SEPARATE PERMIT. |
| | |
| | |
| | |
| | 2) THERE IS SITE PLAN SHOWING THE SPECIFIC LOCATION OF |
| | THE GENERATOR INCLUDING ALL DIMENSIONS TO AREA |
| | BUILDINGS, INCLUDING NEIGHBORING PROPERTIES, AND WINDOW |
| | AND DOOR AND OTHER OPENINGS. |
| | |
| | PER NFPA 110 |
| | |
| | 7.2.2 OUTDOOR EPS INSTALLATIONS. |
| | 7.2.2.1 THE EPS SHALL BE INSTALLED IN A SUITABLE |
| | ENCLOSURE LOCATED |
| | OUTSIDE THE BUILDING AND CAPABLE OF RESISTING THE |
| | ENTRANCE |
| | OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY AS REQUIRED |
| | BY LOCAL BUILDING CODES. |
| | |
| | PLEASE PROVIDE SPECIFIC SITE PLAN DETAILS. |
| | |
| | |
| | |
| | 3) THERE IS NO INDICATION OF GENERATOR CLASSIFICATION |
| | NOR TYPE PER NFPA 110 |
| | |
| | PER NFPA 110 |
| | |
| | CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY |
| | SYSTEMS (EPSSS) |
| | 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF |
| | ELECTRICAL |
| | POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO |
| | LOADS FOR |
| | A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND |
| | WITHIN A SPECIFIED |
| | TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER |
| | SUPPLY |
| | AS SPECIFIED IN TABLE 4.1(B). |
| | 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN |
| | HOURS, FOR |
| | WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD |
| | WITHOUT |
| | BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] |
| | 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN |
| | SECONDS, |
| | THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE |
| | TRANSFER |
| | SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE |
| | 4.1(B) |
| | PROVIDES THE TYPES DEFINED BY THIS STANDARD. |
| | 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF |
| | EQUIPMENT |
| | INSTALLATION, PERFORMANCE, AND MAINTENANCE. |
| | 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| | OF THE |
| | EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE |
| | OR |
| | SERIOUS INJURIES. |
| | 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| | OF THE |
| | EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND |
| | SAFETY. |
| | 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED. |
| | 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT |
| | ALL LOADS |
| | SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER |
| | THAT |
| | MEETS ALL THE FOLLOWING CRITERIA: |
| | (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE |
| | LOAD |
| | (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED |
| | IN TABLE |
| | 4.1(A) |
| | (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED |
| | IN TABLE |
| | 4.1(B) |
| | |
| | PLEASE PROVIDE DETAILS AS THIS IS HOW IT WILL INSPECTED |
| | AND THE ACCEPTANCE TESTING. |
| | |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |