| Plan Review Notes For Permit 19060010 |
| Permit Number |
19060010 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-07-14 04:54:42 | 7/14/2019 2ND PLUMBING REVIEW **DENIED** WITH COMMENTS | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1 )WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR | | | SHUTTING OFF WITHOUT MOVING UNITS, 2017 FBC SEC | | | R2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE | | | SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS | | | PANEL OR SIMILAR REMOVABLE OBSTRUCTION. | | | | | | 2) TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE THE | | | COST OF ALL PLUMBING . PROVIDE BONA FIDE SIGNED | | | CONTRACT PER WPB AMENDMENTS TO THE FBC 109.3 BUILDING | | | PERMIT VALUATIONS. | | | | | | 3) MASTER TUB VALVE MUST PROVIDE PROVISIONS FOR | | | TEMPERED WATER REQUIRED AND DETAILS OF A TEMPERATURE | | | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 FBC P | | | 607.1.2 TEMPERED WATER TEMPERATURE CONTROL. | | | | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | | | | | | | |
|