| Date |
Text |
| 2019-07-14 09:16:59 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN PROVIDED DOES NOT SHOW ANY ELECTRICAL WORK. |
| | ELECTRICAL NOTE 1 STATES THAT AN ELECTRICAL CONTRACTOR |
| | IS RESPONSIBLE FOR FBC COMPLIANCE, HOWEVER, THIS |
| | STATEMENT DOES NOT ALLEVIATE THE RESPONSIBILITY OF |
| | SHOWING ELECTRICAL ON THE PLAN. PROVIDE ELECTRICAL PLAN |
| | FOR REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN |
| | PROFESSIONAL OR SIGNED BY THE ELECTRICAL CONTRACTOR |
| | QUALIFIER. SHOW EXISTING AND PROPOSED RECEPTACLE AND |
| | LIGHTING OUTLETS. FS 471.003(2)(H); 471.025; WPB FBC |
| | 107.2.1, 107.3.5 |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4 |
| | 3. CONTRACT PROVIDED STATES THAT ELECTRICAL IS NOT |
| | INCLUDED. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE |
| | AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR |
| | SO THIS VALUE CAN BE ADDED TO THE TOTAL PERMIT VALUE. |
| | WPB FBC 109.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |