Plan Review Notes
Plan Review Notes For Permit 19060010
Permit Number 19060010
Review Stop P
Sequence Number 1
Notes
Date Text
2019-06-18 14:18:31PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE
 REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL
 PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE
 RE-REVIEW OF SUBMITTED CORRECTIONS
  
 1) BUILDING WAS BUILT IN 2006 UNDER THE FAIR HOUSING
 ACT (FHA) ALL ELEMENTS OF FHA ARE TO REMAIN. YOUR
 BATHROOM CABINET DETAIL SHOW HEIGHT @ 35 3/4". MAX
 PERMITTED IS 34". PLEASE REVIEW THE FAIR HOUSING DESIGN
 MANUAL. SECTION 7.52. ADD NOTE TO PLAN THAT ALL
 INSTALLATIONS SHALL REMAIN AND COMPLY WITH FHA
  
 2) PLANS SHALL BE SIGNED AND SEAL BY DESIGN
 PROFESSIONAL.FS 471, 481. PLANS SHALL BE DIMENSIONAL
 AND HAVE SUFFICIENT CLARITY AND SHOW DETAIL. SEE
 BUILDING REVIEW COMMENTS. FBC 107.2.1
  
 3) PROVIDE KITCHEN CABINET DETAIL. NOTE MAX PERMITTED
 IS 36"
  
 4) PROVIDE SHOWER PAN DETAIL SHOWING WHAT MATERIAL IS
 BEING USED AND FLOOR WILL BE PRE-PITCH @ 2%. FBC
 107.3.5
  
 5) VALUE APPEARS TOO LOW. PROVIDE A SIGN BONA FIDE
 CONTRACT. WPB AMEND 109.3
  
 6) A SUB PLUMBING PERMIT BY A LICENSE PLUMBING
 CONTRACTOR IS REQUIRED. FS 489
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  