| 2019-06-18 14:18:31 | PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE | | | REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL | | | PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE | | | RE-REVIEW OF SUBMITTED CORRECTIONS | | | | | | 1) BUILDING WAS BUILT IN 2006 UNDER THE FAIR HOUSING | | | ACT (FHA) ALL ELEMENTS OF FHA ARE TO REMAIN. YOUR | | | BATHROOM CABINET DETAIL SHOW HEIGHT @ 35 3/4". MAX | | | PERMITTED IS 34". PLEASE REVIEW THE FAIR HOUSING DESIGN | | | MANUAL. SECTION 7.52. ADD NOTE TO PLAN THAT ALL | | | INSTALLATIONS SHALL REMAIN AND COMPLY WITH FHA | | | | | | 2) PLANS SHALL BE SIGNED AND SEAL BY DESIGN | | | PROFESSIONAL.FS 471, 481. PLANS SHALL BE DIMENSIONAL | | | AND HAVE SUFFICIENT CLARITY AND SHOW DETAIL. SEE | | | BUILDING REVIEW COMMENTS. FBC 107.2.1 | | | | | | 3) PROVIDE KITCHEN CABINET DETAIL. NOTE MAX PERMITTED | | | IS 36" | | | | | | 4) PROVIDE SHOWER PAN DETAIL SHOWING WHAT MATERIAL IS | | | BEING USED AND FLOOR WILL BE PRE-PITCH @ 2%. FBC | | | 107.3.5 | | | | | | 5) VALUE APPEARS TOO LOW. PROVIDE A SIGN BONA FIDE | | | CONTRACT. WPB AMEND 109.3 | | | | | | 6) A SUB PLUMBING PERMIT BY A LICENSE PLUMBING | | | CONTRACTOR IS REQUIRED. FS 489 | | | | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|