2019-07-30 11:21:19***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND MECHANICAL REVIEW DENIED:
  
 1. FBC M 503.2 AND FBC M 506.3 PROVIDE SEPERATE PLANS
 SPECIFIC TO HOODS WITH GREASE/EXHAUST AND MAKE-UP AIR
 DUCT DETAILS. THE GREASE DUCT DETAILS NEED TO INCLUDE
 THE IN-LINE EXHAUST FAN (IF USED) FIRE RATED ENCLOSURE
 /FIRE WRAP/ACCESS DOOR INFORMATION.
 2. FBC B 107.2.1 ALL INFORMATION ON CONSTRUCTION
 DOCUMENTS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.