| Plan Review Notes For Permit 19051555 |
| Permit Number |
19051555 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-04 13:32:00 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1.THE ISOMETRIC DRAWING DOES NOT MATCH THE FLOOR PLAN | | | THE ISOMETRIC SHOWS TWO BRANCHES FOR KITCHEN ONE WITH A | | | FLOOR SINK AND FLOOR DRAIN THE OTHER SHOWING THE 3COMP | | | SINK HAND AND MOP SINK. THEY SHALL MATCH. PER WPB AMEND | | | TO FBC 107.2.1 | | | | | | 2. SHOW THE REQUIRED GREASE INTERCEPTOR ON THE | | | ISOMETRIC AND FLLOOR PLAN. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|