| 2019-08-22 16:01:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | 1. SECOND REQUEST: SHOW OR PROVIDE NOTE THAT BOTH |
| | TOILET ROOM SINKS ARE TEMPERED 110F MAX BY AN ASSE 1070 |
| | DEVICE. FBC P 607.1.2; NOTE THAT AFTER REVIEWING |
| | RESPONSE COMMENTS AND THE REVISED PLANS, I COULD NOT |
| | FIND EVIDENCE OF COMPLIANCE. PLEASE PROVIDE NOTE AND |
| | CLOUD AS A REVISION. |
| | 2. FBC ACC 606.3 LAVATORIES AND SINKS SHALL BE |
| | INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR |
| | COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. DIMENSION ON COUNTER DETAIL |
| | SHALL BE TO THE FIXTURE RIM WHICH IS THE HIGHER OF THE |
| | TWO ITEMS. |
| | 3. FOR A CLARIFICATION AND TO ALLOW FOR THE USE OF AN |
| | AIR ADMITTANCE VALVE FOR THE KITCHEN SINK AS OPPOSED TO |
| | PROVIDING A VENT THROUGH THE ROOF, PER WPB FBC 107.2.1, |
| | INDICATE ON THE PLAN VIEW THAT THE UPSTREAM SIDE OF THE |
| | BRANCH CONNECTION TO THE EXTERIOR DRAIN AS WELL AS 5 |
| | FEET PLUS OR MINUS DOWNSTREAM OF THE BRANCH CONNECTION |
| | IS THE "SANITARY BUILDING DRAIN". PROVIDE AND SHOW A |
| | FULL SIZE TWO-WAY CLEANOUT TO GRADE AND DESIGNATE |
| | SANITARY BUILDING SEWER DOWNSTREAM OF THE CLEANOUT. |
| | ADDITIONALLY, INDICATE ON NOTE 1 ON P-1 "EXISTING |
| | BUILDING DRAIN" AS OPPOSED TO "EXISTING". ON THE |
| | SANITARY RISER DIAGRAMS ON P-2, TIE IN NOTES SHOULD SAY |
| | "EXISTING BUILDING DRAIN" AS OPPOSED TO "EXISTING". |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19051536 201 ARKONA CT |
| | |
| | |
| | |