| 2019-06-20 12:14:22 | PLUMBING 1ST REVIEW**DENIED** I WOULD ADVISE THE DESIGN |
| | TEAM COMING IN FOR A MEETING DUE TO THE LARGE AMOUNT OF |
| | COMMENTS SO ALL CAN BE ADDRESSED ON THE 2ND REVIEW. |
| | |
| | 1) PROVIDE OCCUPANT LOAD ON SHT.SP1. FBC 107.3.5 |
| | |
| | 2) SHT.X1 NOTES ADVISES BOTTLE WATER WILL BE PROVIDE |
| | LIEU OF LOW OF A HI-LOW DRINKING FOUNTAIN. FBC P403.1 |
| | REQUIRES UNDER YOUR BUSINESS CLASSIFICATION A DRINKING |
| | FOUNTAIN SHALL BE SUPPLIED UNDER FBC P410.3. WITH YOUR |
| | OCCUPANT LOAD. |
| | |
| | 3) PROVIDE CLEAR FLOOR SPACE AS REQUIRED BY FBC-ACC 606 |
| | AND 608. |
| | (A) THE BAR SINK IN THE CONFERENCE ROOM |
| | (B) THE BREAK ROOM SINK |
| | (C) BATHROOM SHOWER |
| | |
| | 4) A GREASE INTERCEPTOR IS REQUIRED ANY TIME COOKING OR |
| | THE HEATING OF FOOD (GAS STOVE) IS PROVIDED WHICH WOULD |
| | CAUSE THE DISCHARGE OF GREASER TO ENTER THE SEWAGE |
| | SYSTEM. PROVIDE LOCATION, TYPE, SIZE AND HOW YOU CAME |
| | TO SIZE OF THE INTERCEPTOR. FBC P1003.1, 1003.2, |
| | 1003.3.4 |
| | |
| | 5) BREAKROOM SINK IS NOT PERMITTED TO BE USED AS THE |
| | SERVICE SINK. PROVIDE LOCATION AND ADD TO WATER AND |
| | SANITARY ISOMETRIC DRAWING. FBC 403.1, 107.3.5 |
| | |
| | 6) PROVIDE SHOWER DIMENSION ON SHT A4 SHOWER THE |
| | FINISHED SHOWER WILL BE 36" X 36". FBC-ACC 104.1 |
| | |
| | 7) TOILET ROOMS SHALL BE LISTED AS MEN?S AND WOMEN?S. |
| | PLEASE SUPPLY A SHOWER TO THE OTHER TOILET ROOM AS TO |
| | PROVIDE A SHOWER TO THE OPPOSITE SEX TO MEET EQUIVALENT |
| | FACILITATION. FBC-ACC 103 |
| | |
| | 8) TOILET ROOM 105 SHOWS THE LAVATORY ENCROACHING INTO |
| | THE CLEAR FLOOR SPACE OF THE TOILET. OTHER FIXTURES ARE |
| | NOT PERMITTED TO BE IN THE CLEAR FLOOR.FBC-ACC 604.3.2 |
| | |
| | 9) PLAN CALLS OUT FOR A GAS RANGE. A SEPARATE GAS PLAN |
| | AND PERMIT IS REQUIRED. SEE GAS REVIEW COMMENTS. FBC |
| | 105.1 |
| | |
| | 10) SHT. A4.0 SHOW ALL GRAD BAR MOUNTING TO BE 36? TO |
| | THE CENTER. GRAB BARS SHALL BE MOUNTED 33-36? TO THE |
| | TOP OF THE GRIPPING SURFACE. FBC-ACC 609.4 |
| | |
| | 11) SHT A4.0 DETAIL # 2 AND SHT. A6.0 SHOWS ADA SINKS |
| | TO HAVE A KNEE CLEARANCE OF 2? 6? (30) AND A CABINET |
| | WITH DOORS. THE MIN KNEE CLEARANCE PERMITTED IS 27? PER |
| | FBC-ACC AND HAVE A FRONT APPROACH WHICH DOES NOT ALLOW |
| | FOR A CABINET WITH DOORS. FBC-ACC 606.2, FBC-ACC 306.3 |
| | |
| | 12) PROVIDE MIRROR DETAIL SHOWING MOUNTING MAX 40? TO |
| | THE REFLECTIVE SURFACE. FBC-ACC 603.3 AND THE TOILET |
| | PAPER DISPENSER 7?-9? FROM THE FRONT OF THE BOWL. |
| | FBC-ACC 604.7 |
| | |
| | 13) PROVIDE INSTALLATION MANUAL FOR THE SHOWER PAN |
| | MATERIAL CALLED OUT ON SHT. A8.0 (NOBELSEAL) FBC |
| | 107.2.1 |
| | |
| | 14) PROVIDE KITCHEN CABINET AND COUNTER TOP DETAIL. MAX |
| | HEIGHT PERMITTED IS 34? AND SHOW THAT YOU MEET ALL |
| | REACH RANGES. FBC-ACC 606.3, FBC-ACC 308 |
| | |
| | 15) SHOW OR PROVIDE NOTE THAT BOTH TOILET ROOM SINKS |
| | ARE TEMPERED 110F MAX BY AN ASSE 1070 DEVICE. FBC P |
| | 607.1.2 |
| | |
| | 16) SHT. P1.0 CALLS OUT OF FOR TANKLESS TO BE 3.5 KW. |
| | PROVIDE HEAT RISE CHART SHOWING HEATER IS CAPABLE OF |
| | PRODUCING 2.2 GPM OF HOT WATER MIN 110F. FBC P 607.1 |
| | |
| | 17) SHT. P-2 SHOWS KITCHEN AS BEING VENTED BY AAV. SHT |
| | P1 CALLS FOR THIS TO BE A NEW BUILDING DRAIN. THIS LINE |
| | MUST ALSO CONNECT INTO A GREASE INTERCEPTOR WHICH BOTH |
| | REQUIRED A VENT EXTEND TO THE OUTDOORS. FBC P904.1, AND |
| | THE INSTALLATION MANUAL OF THE INTERCEPTOR. FBC P |
| | 1003.3.4 |
| | |
| | 18) SHT P2 BATHROOM GROUP 105 SHOWS THE BAR SINK |
| | DISCHARGING INTO THE BATHROOM GROUP WET VENT. ONLY |
| | THOSE FIXTURES LOCATED IN THE BATROOM OR 1 OTHER |
| | BATHROOM GROUP ARE PERMITTED TO DISCHARGE INTO THE |
| | BATHROOM GROUP WET VENT. ALL OTHERS SHALL DISCHARGE |
| | DOWN STREAM OF THE BATHROOM GROUP. FBC P 912.1 |
| | |
| | 19) PROVIDE SHOWER VALVES INSTALLATION MANUAL OR NOTE |
| | ON PLAN SHALL BE PRESSURE BALANCED/ THERMO ASSE 1016 |
| | APPROVED WITH INTEGRAL SHUT OFF VALVES. FBC P 434.3. |
| | |