| Plan Review Notes For Permit 19051536 |
| Permit Number |
19051536 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-03 10:32:23 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) PLEASE SHOW DETAIL OF OUTLET AND LIGHTING CONTROL | | | PER FBC ENERGY CODE | | | | | | 2) ALL 120 VOLT 15 AND 20 AMPERE OUTLETS IN THE KITCHEN | | | TO BE GFCI PROTECTED | | | | | | 210.8(B) OTHER THAN DWELLING UNITS. ALL 125-VOLT, | | | SINGLE-PHASE, | | | 15- AND 20-AMPERE RECEPTACLES INSTA LLED IN THE | | | LOCATIONS SPECIFIED | | | IN 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT | | | CIRCUITINTERRUPTER | | | PROTECTION FOR PERSONNEL. (2) KITCHENS |
|