| 2021-12-16 15:43:57 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-19051525 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS NEW SCOPE OF WORK HAS INCREASED THE VALUE OF |
| | THE ORIGINAL PROJECT. PLEASE SUBMIT A NEW PLAN REVIEW |
| | REQUEST FORM SHOWING THE NEW REVISED VALUE OF THIS |
| | PROJECT. FBC 107.2.1 |
| | |
| | 2) NOTHING ABOUT THE HOOD OR THE REFRIGERATION WILL BE |
| | REVIEWED UNDER THIS PERMIT. A SEPARATE PERMIT FOR EACH |
| | WILL BE REQUIRED. |
| | |
| | 3) SHEET M1.03: THE MEASUREMENT FROM THE HOOD EXHAUST |
| | TERMINATION TO THE MUA INTAKE IS SHOWING A MEASUREMENT |
| | OF 8 FT 7 INCHES, PLEASE SHOW THIS CLEARANCE MEETS THE |
| | 10 FEET MINIMUM. FBC M 401.4 |
| | |
| | 4) PLEASE SHOW THE RETURN AIR PATH FROM THE KITCHEN TO |
| | AHU-3. FBC M 601.6 |
| | |
| | 5) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS FOR THE MECHANICAL SYSTEMS. FBC EC |
| | C403.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |