| 2021-12-17 10:37:17 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 19051525 |
| | 12/17/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P101: THE SUBMITTED INCREASED SCOPE OF WORK |
| | INDICATES THE KITCHEN WILL BE INSTALLED. PLEASE REMOVE |
| | THE "FUTURE" LABELS FOR THE PLUMBING FIXTURES AND |
| | APPLIANCES- SECTION 107.2.1 WPB. |
| | |
| | 2) P101, 338 A: THE HAND SINKS (B04) (K10), AND |
| | DRAINAGE FROM THE ICE MACHINE (B02) AND THE ICE BIN |
| | (B08) SHALL NOT DISCHARGE INTO THE GREASE WASTE LINE |
| | AND GREASE INTERCEPTOR- SECTION 1003.3.1 FBC P. GREASE |
| | INTERCEPTORS SHALL RECEIVE WASTE ONLY FROM FIXTURES AND |
| | EQUIPMENT THAT ALLOW FATS, OIL OR GREASE TO BE |
| | DISCHARGED. |
| | |
| | 3) P101: PROVIDE A PLUMBING FIXTURE SCHEDULE FOR THE |
| | RESTROOMS- SECTION 107.2.1 WPB. THE ARCHITECTURAL PLANS |
| | APPEAR TO SHOW WATER CLOSETS WITH FLUSH VALVES WHICH |
| | REQUIRE 1-INCH SUPPLY PIPES. THE PLUMBING PLAN AND |
| | ISOMETRIC DRAWING ARE INDICATING 3/4-INCH PIPES- SEE |
| | TABLE 604.5 FBC P. |
| | |
| | 4) P101 & P301: SHOW THE HWR LINE ON THE PLUMBING FLOOR |
| | PLAN AND IN THE ISOMETRIC DRAWING- SECTION 607.2 FBC P, |
| | AND C404.5.1 FBC EC. |
| | |
| | 5) P101 & P201: PROVIDE TRAFFIC RATED LIDS FOR THE |
| | GREASE INTERCEPTOR ACCESS OPENINGS, AND THE SAMPLING |
| | PORT- SECTION 305.6 FBC P. PLEASE NOTE THAT SPECS FOR |
| | THE LIDS AND FOR THE GREASE INTERCEPTORS SHALL BE |
| | SUBMITTED UNDER THE REQUIRED SEPARATE GREASE |
| | INTERCEPTOR PERMIT- SECS.105.1 & 107.2.1 WPB. |
| | |
| | 6) P102- ROOF AND STORM DRAINAGE PLANS ARE INCOMPLETE. |
| | A) INDICATE THE RAINFALL RATE PER SEC. 1106.1 AND |
| | PROVIDE ROOF DRAINAGE CALCULATIONS BASED ON THE RATE- |
| | SECS. 1106.1- 1106.4 FBC P. |
| | B) VERIFY THE ROOF AND DRAINAGE SYSTEM HAS BEEN |
| | DESIGNED IN COMPLIANCE WITH SECTION 1101.7 FOR MAXIMUM |
| | DEPTH OF PONDING WATER AND DEFLECTED STRUCTURAL |
| | ELEMENTS. |
| | C) PROVIDE PRIMARY AND EMERGENCY SCUPPER AND DOWN SPOUT |
| | SIZES- TABLE 1106.3 & SECS.1106.5, 1108.1 FBC P. PLEASE |
| | INCLUDE CONSTRUCTION DETAILS OR INSTALLATION DETAILS |
| | FOR MANUFACTURED PRODUCTS- SEC. 107.2.1 WPB. |
| | D) SHOW THE DOWNSPOUT DISCHARGE LOCATIONS. CLARIFY IF |
| | THE DOWNSPOUTS WILL CONNECT TO AN UNDERGROUND STORM |
| | DRAIN SYSTEM OR BE DISCHARGED TO GRADE. PLEASE PROVIDE |
| | CIVIL DRAWINGS SHOWING STORM DRAINAGE POINTS OF |
| | CONNECTIONS (IF APPLICABLE), OR REFER TO SEC. 1503.7 |
| | FBC B AND INDICATE THE DOWNSPOUTS WILL DISCHARGE AT |
| | LEAST 1 FOOT AWAY FROM THE BUILDING SIDE WALL TO |
| | APPROVED LOCATIONS OF DISPOSAL- SEC.1101.2 FBC P. |
| | |
| | 7) SHEETS 340A-A, 341A-A- FBC ACC COMPLIANCES: |
| | A) SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS |
| | FOR THE WATER CLOSETS- SEC. 604.3. |
| | B) SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS |
| | FOR THE LAVATORIES- 606.2. |
| | C) SHOW THE TURNING SPACE DIAMETERS- 304.3. |
| | D) THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACES REQUIRED FOR THE WATER CLOSETS- 603.2.3 |
| | E) SHOW THE HEIGHTS OF THE WATER CLOSET SEATS FROM THE |
| | FINISHED FLOORS- SECTION 604.4. |
| | F) SHOW THE KNEE AND TOE CLEARANCES FOR THE LAVATORIES- |
| | 606.2, AND FIGURES 306.2 & 306.3. |
| | |
| | 8) SHEETS 315A, 340A-A, 341A-A: PROVIDE THE TYPE OF |
| | FINISH MATERIALS TO BE INSTALLED AT THE WALL SURROUNDS |
| | FOR THE WATER CLOSETS, URINALS, AND SERVICE SINK. |
| | PLEASE NOTE THAT THE MATERIAL SURFACES SHALL BE SMOOTH, |
| | HARD AND NONABSORBENT IN COMPLIANCE WITH SEC. 310.3 FBC |
| | P, AND 1210.2.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |