| Plan Review Notes For Permit 19051525 |
| Permit Number |
19051525 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-03-02 18:05:40 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | THIRD BUILDING REVIEW DENIED: | | | | | | APPROVAL IS PENDING THE CORRECTION OF THE FOLLOWING | | | ITEMS FROM THE LAST REVIEW: | | | | | | 1A)(2) PROVIDE ALL SET BACKS FROM PROPERTY LINE | | | INCLUDING EDGE OF PROPOSED WORK ON SURVEY. | | | | | | 1B) PROVIDE THE UNITY OF TITLE. THE UNITY OF TITLE IS | | | REQUIRED PRIOR TO ISSUANCE OF PERMIT. | | | | | | 2A) ON PAGE 307 LS PLEASE CORRECT THE BASED ON SEATS | | | LAYOUT TOTAL OCCUPANT LOAD FROM 150 TO 138. |
|