| 2019-07-24 14:58:32 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE WATER ISOMETRIC DOES NOT MATCH THE SITE PLAN IT |
| | IS MISSING THE HOSE BIB IN THE TRASH ENCLOSURE PLEASE |
| | CORRECT ISOMETRIC. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 2. STORM WATER SHALL NOT DISCHARGE TO THE SANITARY THE |
| | FLOOR DRAIN IN THE TRASH ENCLOSURE SHALL NOT RECEIVE |
| | STORM WATER. WEST PALM BEACH, FLORIDA - CODE OF |
| | ORDINANCES SEC. 90-126(5) |
| | |
| | 3. THE FLOOR DRAIN IN TRASH ENCLOSURE IS MISSING ON THE |
| | SANITARY ISOMETRIC AND ALSO REQUIRES A TRAP PRIMER. PER |
| | FBC PL 1002.4.1 |
| | |
| | THE GREASE WASTE SHOULD NOT DISCHARGE THROUGH THE SAND |
| | OIL SEPARATOR UNLESS APPROVED BY SCHIER. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |