| 2019-06-25 13:56:10 | MECHANICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. THERE IS NO RECORD OF THE 10X12 A/C VENT BEING |
| | PERMITTED. SHOW AS PROPOSED AND INCLUDE IN ENERGY |
| | CALCULATIONS FOR SYSTEM SIZING. |
| | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| | STORIES. |
| | |
| | 2. PROVIDE MECHANICAL RISER DIAGRAHM. INCLUDE THE |
| | PROPOSED 10X12 VENT AND REQUIRED RETURN AIR VENT. |
| | FBC E R403.7.1EQUIPMENT SIZING. |
| | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN SECTION R302.1 |
| | |
| | 3. NOTE ON PLAN STATES SYSTEM IS A 4 TON UNIT. PROVIDE |
| | MAKE AND MODEL NUMBER OF AHU & CU. |
| | M1202.1ADDITIONS, ALTERATIONS OR REPAIRS. |
| | ADDITIONS, ALTERATIONS, RENOVATIONS OR REPAIRS TO A |
| | MECHANICAL SYSTEM SHALL CONFORM TO THE REQUIREMENTS FOR |
| | A NEW MECHANICAL SYSTEM WITHOUT REQUIRING THE EXISTING |
| | MECHANICAL SYSTEM TO COMPLY WITH ALL OF THE |
| | REQUIREMENTS OF THIS CODE. ADDITIONS, ALTERATIONS OR |
| | REPAIRS SHALL NOT CAUSE AN EXISTING MECHANICAL SYSTEM |
| | TO BECOME UNSAFE, HAZARDOUS OR OVERLOADED. MINOR |
| | ADDITIONS, ALTERATIONS OR REPAIRS TO EXISTING |
| | MECHANICAL SYSTEMS SHALL MEET THE PROVISIONS FOR NEW |
| | CONSTRUCTION, UNLESS SUCH WORK IS DONE IN THE SAME |
| | MANNER AND ARRANGEMENT AS WAS IN THE EXISTING SYSTEM, |
| | IS NOT HAZARDOUS, AND IS APPROVED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |