Plan Review Notes
Plan Review Notes For Permit 19051482
Permit Number 19051482
Review Stop P
Sequence Number 3
Notes
Date Text
2019-12-20 12:00:441) SHT. 8 OF THE ENERGY CALCS NOTE THAT THE MINIMUM EF
 RATING IS .92. THE MINIMUM REQUIRED RATING IS .95 AS OF
 APRIL 16, 2015 PER THE DEPT. OF ENERGY CHANGE TO 10 CFR
 PART 430.32. PLEASE CHANGE THE MINIMUM EFFICIENCY TO
 READ THE MINIMUM OF .95. I AM AWARE THE THE UNIT BEING
 SUPPLIED GAS A DESIGN EF OF .98.
 2) SHT.LS 1.0 - TEACHING KITCHEN - THE PLAN SHOWS AN
 OCCUPANT LOAD AS 12 BUT THE OCCUPANT LOAD CALCULATION
 TABLE NOTES 19 UNDER THE 2017 FBC HEADING. CLARIFY.
 3) SHT. P1.1 - KEYNOTE #1 STATES THE SANITARY DRAIN TO
 CONNECT TO THE GREASE WASTE SYSTEM. THE SANITARY CANNOT
 CONNECT TO THE GREASE WASTE SYSTEM PER 2017
 FBC-PLUMBING SEC.1003.2. THIS IS OBVIOUSLY A
 TYPOGRAPHICAL ERROR AS THE PLAN SHOWS THE CORRECT
 ARRANGEMENT. REVISE THE NOTE.
 4) SHT. P1.1 - REFERS TO CIVIL PLANS FOR THE BUILDING
 SEWER. CIVIL PLANS HAVE NOT BEEN INCLUDED IN THIS
 SUBMITTAL. CLARIFY.
 5) SIZE THE VENT STACK BY THE ICE MACHINE.
 6) SHT. P-2.1 - REFERS TO A ONE INCH DOMESTIC WATER
 SUPPLY LINE BUT THE PLAN SHOWS AN ONE AND ONE-QUARTER
 INCH LINE. CLARIFY.
 7) SHT. P-3.1 - DETAIL #1 - EACH WELL OF A MULTIPLE
 COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLT TO A
 WASTE RECEPTOR. 2017 FBC-PLUMBING SEC.802.1.1.
 8) THE HOT WATER RETURN LINE SHALL BE INSTALLED IN
 ACCORDANCE WITH THE 2017 FBC-PLUMBING SEC.607.2.2.
 9) THE PREVIOUS REVIEW REFERS TO THE GREASE WASTE
 SYSTEM AS DESIGNED AS A COMBINATION WATSE AND VENT
 SYSTEM WHICH PROHIBITS THE DISCHARGE FROM A FOOD WASTE
 DISPOSER PER 2017 FBC-PLUMBING SEC.915.1.. THERE IS NOT
 EXCEPTION FOR THE USE OF A SOLIDS INTERCEPTOR AS AN
 EXCEPTION OR ALTERNATIVE METHOD. THE
 MAINTENANCE/CLEANING OF SUCH SOLIDS INTERCEPTOR CANNOT
 BE MONITORED FOR COMPLIANCE THEREFORE THE FOOD DISPOSER
 INSTALLATION IS PROHIBITED.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW