| 2019-12-20 12:00:44 | 1) SHT. 8 OF THE ENERGY CALCS NOTE THAT THE MINIMUM EF |
| | RATING IS .92. THE MINIMUM REQUIRED RATING IS .95 AS OF |
| | APRIL 16, 2015 PER THE DEPT. OF ENERGY CHANGE TO 10 CFR |
| | PART 430.32. PLEASE CHANGE THE MINIMUM EFFICIENCY TO |
| | READ THE MINIMUM OF .95. I AM AWARE THE THE UNIT BEING |
| | SUPPLIED GAS A DESIGN EF OF .98. |
| | 2) SHT.LS 1.0 - TEACHING KITCHEN - THE PLAN SHOWS AN |
| | OCCUPANT LOAD AS 12 BUT THE OCCUPANT LOAD CALCULATION |
| | TABLE NOTES 19 UNDER THE 2017 FBC HEADING. CLARIFY. |
| | 3) SHT. P1.1 - KEYNOTE #1 STATES THE SANITARY DRAIN TO |
| | CONNECT TO THE GREASE WASTE SYSTEM. THE SANITARY CANNOT |
| | CONNECT TO THE GREASE WASTE SYSTEM PER 2017 |
| | FBC-PLUMBING SEC.1003.2. THIS IS OBVIOUSLY A |
| | TYPOGRAPHICAL ERROR AS THE PLAN SHOWS THE CORRECT |
| | ARRANGEMENT. REVISE THE NOTE. |
| | 4) SHT. P1.1 - REFERS TO CIVIL PLANS FOR THE BUILDING |
| | SEWER. CIVIL PLANS HAVE NOT BEEN INCLUDED IN THIS |
| | SUBMITTAL. CLARIFY. |
| | 5) SIZE THE VENT STACK BY THE ICE MACHINE. |
| | 6) SHT. P-2.1 - REFERS TO A ONE INCH DOMESTIC WATER |
| | SUPPLY LINE BUT THE PLAN SHOWS AN ONE AND ONE-QUARTER |
| | INCH LINE. CLARIFY. |
| | 7) SHT. P-3.1 - DETAIL #1 - EACH WELL OF A MULTIPLE |
| | COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLT TO A |
| | WASTE RECEPTOR. 2017 FBC-PLUMBING SEC.802.1.1. |
| | 8) THE HOT WATER RETURN LINE SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE 2017 FBC-PLUMBING SEC.607.2.2. |
| | 9) THE PREVIOUS REVIEW REFERS TO THE GREASE WASTE |
| | SYSTEM AS DESIGNED AS A COMBINATION WATSE AND VENT |
| | SYSTEM WHICH PROHIBITS THE DISCHARGE FROM A FOOD WASTE |
| | DISPOSER PER 2017 FBC-PLUMBING SEC.915.1.. THERE IS NOT |
| | EXCEPTION FOR THE USE OF A SOLIDS INTERCEPTOR AS AN |
| | EXCEPTION OR ALTERNATIVE METHOD. THE |
| | MAINTENANCE/CLEANING OF SUCH SOLIDS INTERCEPTOR CANNOT |
| | BE MONITORED FOR COMPLIANCE THEREFORE THE FOOD DISPOSER |
| | INSTALLATION IS PROHIBITED. |
| | |
| | |