| 2019-06-21 08:11:42 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE TRAINING KITCHEN SHALL COMPLY WITH FBC ACC 804 |
| | PER FBC ACC 212.2 PLEASE SHOW COMPLIANCE WITH ALL |
| | SECTIONS OF 804 |
| | |
| | 2. THE THREE COMP SINK SHALL COMPLY WITH FBC ACC 606.2 |
| | |
| | 3. SHT. P1.2, P2.1, P2.2 THE SHEETS DID NOT LOAD |
| | PROPERLY THE LABELS ON SOME OF THE FIXTURES ON THE |
| | ISOMETRIC DRAWING ARE MISSING AND THE FIXTURES IN THE |
| | CLASS ROOMS ARE MISSING LABELS PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 4. A LINT INTERCEPTOR IS REQUIRED ON THE WASHING |
| | MACHINE PER FBC PL 1003.6 |
| | |
| | 5. PLEASE SHOW TRAP PRIMERS ON THE SANITARY ISOMETRIC . |
| | PER FBC PL 1002.4.1 |
| | |
| | 6. SHT P2.2 SHUT OFF VALVES ARE REQUIRED ON ALL HOT AND |
| | COLD DROPS PLEASE SHOW ON THE ISOMETRIC DRAWINGS PER |
| | FBC PL 606.1(5) |
| | |
| | 7. WHAT IS THE M1 SHOWN IN THE CLASSROOMS THEY ARE ONLY |
| | SHOWN ON THE WATER RISER AND FLOOR PLAN NOT ON THE |
| | SANITARY PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. SHT. P3.1 DETAIL SHOWS A MIXING VALVE WITH A 110 |
| | DEG. LINE THAT IS NOT SHOWN ON THE WATER PLAN OR |
| | ISOMETRIC PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. SHT. P0.0 THE PLUMBING FIXTURE SCHEDULE IS CALLING |
| | OUT A WATER COOLER FOR IM-1 THE REST OF THE PLAN SHOWS |
| | AN ICE MACHINE PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |