2019-06-28 11:26:431ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19051482
 6/28/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: SHOW THE DS DETECTOR IN THE SUPPLY
 SYSTEM OF RTU-1-4- SECTION 606.2.1 FBC M.
  
 2) M2.1, LS-1: NOTE #2 EXCEPTION TO SECTION 607.5.4
 CORRIDOR/SMOKE BARRIERS IS NOT RELEVANT TO SMOKE
 PARTITIONS. PLEASE REFER TO SECTION 607.5.7 AND CORRECT
 THE NOTE.
  
 3) M2.2: PROVIDE A MINIMUM 5' CLEARANCE FROM THE KEF-1
 DISCHARGE TO RTU-1-1 CURB- SECTION 506.3.13.3 EXCEPTION
 FBC M.
  
 4) M2.2: CORRECT NOTE #1- MINIMUM 4' SUPPORT SPACING
 FOR THE PVC CONDENSATE PIPING REQUIRED PER TABLE 305.4
 FBC M.
  
 5) M5.3 & S1.1: SUBMIT THE NOA FOR THE THYBAR CURB WITH
 SHOP DRAWING APPROVAL BY THE ENGINEER OF RECORD-
 SECTION 107.2.1 WPB.
  
 6) M5.3: SUBMIT NOA #16-0209.03 FOR THE FAN CURB ITH
 SHPOP DRAWING APPROVAL BY THE EOR- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  