| 2019-06-28 11:26:43 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19051482 |
| | 6/28/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M2.1: SHOW THE DS DETECTOR IN THE SUPPLY |
| | SYSTEM OF RTU-1-4- SECTION 606.2.1 FBC M. |
| | |
| | 2) M2.1, LS-1: NOTE #2 EXCEPTION TO SECTION 607.5.4 |
| | CORRIDOR/SMOKE BARRIERS IS NOT RELEVANT TO SMOKE |
| | PARTITIONS. PLEASE REFER TO SECTION 607.5.7 AND CORRECT |
| | THE NOTE. |
| | |
| | 3) M2.2: PROVIDE A MINIMUM 5' CLEARANCE FROM THE KEF-1 |
| | DISCHARGE TO RTU-1-1 CURB- SECTION 506.3.13.3 EXCEPTION |
| | FBC M. |
| | |
| | 4) M2.2: CORRECT NOTE #1- MINIMUM 4' SUPPORT SPACING |
| | FOR THE PVC CONDENSATE PIPING REQUIRED PER TABLE 305.4 |
| | FBC M. |
| | |
| | 5) M5.3 & S1.1: SUBMIT THE NOA FOR THE THYBAR CURB WITH |
| | SHOP DRAWING APPROVAL BY THE ENGINEER OF RECORD- |
| | SECTION 107.2.1 WPB. |
| | |
| | 6) M5.3: SUBMIT NOA #16-0209.03 FOR THE FAN CURB ITH |
| | SHPOP DRAWING APPROVAL BY THE EOR- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |