Plan Review Notes
Plan Review Notes For Permit 19051482
Permit Number 19051482
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-25 10:02:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.0 - RM 110 A STO IS INDICATED WITH A
 ENTRANCE WALLL OF W1 AND REAR WALL OF W3. THE W2A WALL
 ENDS AT THE STO CORNER AND EXTENDS ALONG THE STO SIDE
 ENDING AT THE W3 WALL LEAVING THE W2A WALL PROTECTION
 BROKEN INSIDE THE STO ROOM. EITHER THE FRONT STO ROOM
 WALL AND DOOR NEED TO MEET THE W2A PROTECTION OF THE
 BACK W3 WALL NEEDS TO BE W2A.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 1A) THERE APPEARS TO BE CONFUSION WITH OCCUPANCY LOAD
 CALCULATIONS ARE NOTED IN BUILDING PLAN REVIEW
 COMMENTS.
  
 TO REDUCE DUPILCATE COMMENTS PLEASE ADDRESS THOSE
 COMMENTS.
  
  
  
  
 2) SHEET LS 1.0 - BUSINESS IS INDICATED AS THE MAIN
 OCCUPANCY; HOWEVER, IT IS CLEAR THAT EDUCATION IS THE
 MAIN OCCUPANCY AND OTHER ACCESSORY.
  
 PER NFPA 101
  
 6.1.3.1* DEFINITION ? EDUCATIONAL OCCUPANCY. AN
 OCCUPANCY USED
 FOR EDUCATIONAL PURPOSES THROUGH THE TWELFTH GRADE BY
 SIX OR MORE
 PERSONS FOR 4 OR MORE HOURS PER DAY OR MORE THAN 12
 HOURS PER WEEK.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 3) SHEET MK 7.1 - THERE IS AN INDICATION OF A HOOD
 SYSTEM. THE HOOD SYSTEM SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OD SEPARATE PERMIT AS
 YOU DID FOR THE FIRE SUPPRESSION SYSTEM.
  
  
  
 4) E 3.1 - THERE IS NO INDICATION OF A PULL STATION ON
 THE WEST DOOR LEADING TOWARD THE AUDITORIUM. THOUGH THE
 FIRE ALARM IS UNDER SEPARATE PERMIT, PLEASE PROVIDE AND
 PULL STATION INDICATION HERE FOR REFERENCE PURPOSES.
  
 PER NFPA 101, CH 14 NEW EDUCATIONAL OCCUPANCIES AND CH
 9 BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT
  
 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 14.3.4.1 GENERAL.
 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE
 ALARM SYSTEM IN ACCORDANCE WITH SECTION 9.6.
  
 9.6.2.3 A MANUAL FIRE ALARM BOX SHALL BE PROVIDED AS
 FOLLOWS,
 UNLESS MODIFIED BY ANOTHER SECTION OF THIS CODE:
 (1) FOR NEW ALARM SYSTEM INSTALLATIONS, THE MANUAL FIRE
 ALARM
 BOX SHALL BE LOCATED WITHIN 60 IN. (1525 MM) OF EXIT
 DOORWAYS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL