| Date |
Text |
| 2019-06-25 10:02:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 1.0 - RM 110 A STO IS INDICATED WITH A |
| | ENTRANCE WALLL OF W1 AND REAR WALL OF W3. THE W2A WALL |
| | ENDS AT THE STO CORNER AND EXTENDS ALONG THE STO SIDE |
| | ENDING AT THE W3 WALL LEAVING THE W2A WALL PROTECTION |
| | BROKEN INSIDE THE STO ROOM. EITHER THE FRONT STO ROOM |
| | WALL AND DOOR NEED TO MEET THE W2A PROTECTION OF THE |
| | BACK W3 WALL NEEDS TO BE W2A. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 1A) THERE APPEARS TO BE CONFUSION WITH OCCUPANCY LOAD |
| | CALCULATIONS ARE NOTED IN BUILDING PLAN REVIEW |
| | COMMENTS. |
| | |
| | TO REDUCE DUPILCATE COMMENTS PLEASE ADDRESS THOSE |
| | COMMENTS. |
| | |
| | |
| | |
| | |
| | 2) SHEET LS 1.0 - BUSINESS IS INDICATED AS THE MAIN |
| | OCCUPANCY; HOWEVER, IT IS CLEAR THAT EDUCATION IS THE |
| | MAIN OCCUPANCY AND OTHER ACCESSORY. |
| | |
| | PER NFPA 101 |
| | |
| | 6.1.3.1* DEFINITION ? EDUCATIONAL OCCUPANCY. AN |
| | OCCUPANCY USED |
| | FOR EDUCATIONAL PURPOSES THROUGH THE TWELFTH GRADE BY |
| | SIX OR MORE |
| | PERSONS FOR 4 OR MORE HOURS PER DAY OR MORE THAN 12 |
| | HOURS PER WEEK. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 3) SHEET MK 7.1 - THERE IS AN INDICATION OF A HOOD |
| | SYSTEM. THE HOOD SYSTEM SHALL BE INSTALLED UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OD SEPARATE PERMIT AS |
| | YOU DID FOR THE FIRE SUPPRESSION SYSTEM. |
| | |
| | |
| | |
| | 4) E 3.1 - THERE IS NO INDICATION OF A PULL STATION ON |
| | THE WEST DOOR LEADING TOWARD THE AUDITORIUM. THOUGH THE |
| | FIRE ALARM IS UNDER SEPARATE PERMIT, PLEASE PROVIDE AND |
| | PULL STATION INDICATION HERE FOR REFERENCE PURPOSES. |
| | |
| | PER NFPA 101, CH 14 NEW EDUCATIONAL OCCUPANCIES AND CH |
| | 9 BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT |
| | |
| | 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 14.3.4.1 GENERAL. |
| | 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED |
| | WITH A FIRE |
| | ALARM SYSTEM IN ACCORDANCE WITH SECTION 9.6. |
| | |
| | 9.6.2.3 A MANUAL FIRE ALARM BOX SHALL BE PROVIDED AS |
| | FOLLOWS, |
| | UNLESS MODIFIED BY ANOTHER SECTION OF THIS CODE: |
| | (1) FOR NEW ALARM SYSTEM INSTALLATIONS, THE MANUAL FIRE |
| | ALARM |
| | BOX SHALL BE LOCATED WITHIN 60 IN. (1525 MM) OF EXIT |
| | DOORWAYS. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |