| 2019-10-07 09:21:17 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | 1. THERE IS WORK SHOWN IN THE SCOPE OF WORK THAT DOES | | | NOT HAVE A PERMIT APPLICATION AND REQUIRES A GENERAL | | | CONTRACTOR. PROVIDE PERMIT APPICATION AND PLANS FOR | | | REVIEW. WPB FBC 105.1, 107.1 | | | 2. THERE IS SUBSTANTIAL INFORMATION LACKING IN PLAN | | | SUBMISSION. PROVIDE A PLAN FROM AN ELECTRICAL ENGINEER. | | | WPB FBC 107.1 | | | 3. NO OUTLETS SHOWN BY SINK, OUTLWETS NEED TO BE SHOWN | | | AT LOCATION OF EACH FOR COUNTER SPACING. 210.52 |
|