Plan Review Notes
Plan Review Notes For Permit 19051456
Permit Number 19051456
Review Stop E
Sequence Number 3
Notes
Date Text
2019-12-04 09:22:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (NOT
 CORRECTED, NO RESPONSE PROVIDED.)
  
 NEW COMMENTS:
  
 4. PROVIDE CLARIFICATION FOR RISER DIAGRAM. RISER SHOWS
 AN EXISTING PANEL B WITH A J-BOX UNDERNEATH THAT WILL
 FEED NEW PANEL A, BUT THE RISER ALSO SHOWS AN EXISTING
 PANEL A. WILL PANEL B REMAIN, OR WILL IT BE
 REPLACED/RELOCATED? WILL THERE BE TWO PANEL A'S? THE
 RISER IS CONFUSING. PROVIDE CORRECTIONS. NEC 215.5; WPB
 FBC 107.2.1
 5. AN EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED TO BE
 INSTALLED AFTER THE FIRST MEANS OF DISCONNECT. PROVIDE
 CORRECTION. NEC 250.24, 250.110, 250.118, 250.122
 6. FOR RE-WORK OF ELECTRICAL SERVICE, PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 IS ADEQUATE. NEC 110.9, 110.10
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. LOAD CALCULATION AND PANEL SCHEDULES SHOW THE SYSTEM
 AS 120/240 VOLT 3 PHASE. THIS SYSTEM WOULD HAVE A HIGH
 LEG ON B PHASE AND 120 VOLT LOAD COULD NOT BE CONNECTED
 TO THIS. THIS WOULD ALSO REQUIRE MARKING OF B PHASE PER
 NEC 110.15. IS THIS IN FACT A HIGH LEG SYSTEM? OR IS
 THIS A 120/208 VOLT 3 PHASE SYSTEM? PROVIDE
 CLARIFICATION AND CORRECTIONS AS NEEDED. NEC 110.3,
 110.15, 215.5, 408.30; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  