| Date |
Text |
| 2019-10-25 15:43:48 | 2ND REVIEW: 19051456 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. CITY RECORDS SHOW THE LAST LEGAL OCCUPANCY FOR THIS |
| | BUILDING WAS A BUSINESS THAT MAKES THIS PROJECT A |
| | CHANGE OF OCCUPANCY SHALL COMPLY WITH FBC EXISTING |
| | 1006.1 GENERAL. ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| | UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL |
| | COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ACCESSIBILITY. |
| | |
| | 2. SHT. A-4 BATHROOMS 1-2-3 ARE NOT COMPLIANT WITH |
| | CURRENT FBC ACC IN THE GANG BATHROOMS THE ACCESSIBLE |
| | STALL IS NOT WIDE ENOUGH THE CLEAR FLOOR SPACE FOR THE |
| | TOILET SHALL NOT HAVE ANY OTHER FIXTURES ENCROACHING |
| | INTO IT. IT SHALL COMPLY WITH FBC ACC 604.3.2 604.3.1 |
| | SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 |
| | INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 3. PER FBC PL TABLE 403.1 2 TOILETS AND 2 LAVATORY'S |
| | ARE REQUIRED FOR EACH SEX IN SUITE A. SEPARATE |
| | FACILITIES REQUIRED PER FBC PL 403.2 EACH BATHROOM |
| | SHALL HAVE A COMPLIANT ACCESSIBLE TOILET STALL PER FBC |
| | ACC 213.3.1 |
| | |
| | 4. SEPARATE FACILITIES REQUIRED IN SUITE B PER PER FBC |
| | PL 403.2 |
| | |
| | 5. MOP SINK IS REQUIRED IN SUITE A PER FBC PL TABLE |
| | 403.1 |
| | |
| | 6. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL. THE |
| | REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 7. SHOW COMPLIANCE WITH FBC ACC 604.6 FLUSH CONTROLS. |
| | FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| | WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE |
| | COMPARTMENTS COMPLYING WITH 604.8.2. |
| | |
| | 8. SHOW TANKLESS WATER HEATER ON THE FLOOR PLAN. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION |
| | GUIDE FOR TANKLESS WATER HEATER. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 10. THE SANITARY RISER HAS MULTIPLE CODE VIOLATIONS. |
| | LABEL EXISTING PIPING AND NEW PIPING PER WPB AMEND TO |
| | FBC 107.2.1 |
| | A)THE NEW WATER FOUNTAIN BRANCH DRAIN SHALL CONNECT TO |
| | THE BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP. |
| | PER FBC PL 912.1 |
| | B) THE TOILETS SHALL BE VENTED BEFORE CONNECTING TO THE |
| | BUILDING DRAIN. PER FBC PL 901.2.1, 912.1 |
| | |
| | 11. SEPARATE WATER RISER BETWEEN THE TWO SUITES, EACH |
| | SUITE SHALL HAVE A SEPARATE SHUT OFF VALVE ON THE MAIN |
| | WATER SUPPLY. PER FBC PL 606.1(2) |
| | |
| | 12. SHUT OFF VALVW ARE REQUIRED AT EACH HOT AND COLD |
| | WATER DROP. PER FBC PL 606.1(5) |
| | |
| | |
| | 13.TOILET ROOM NEAR BREAKROOM EXISTING AND NEW PLAN IS |
| | NOT PER CITY RECORDS (#03070117) AND FBC-ACC 604.8.1.7 |
| | REQUIRES THE TOILET TO BE DIAGONAL TO THE DOOR. |
| | |
| | |
| | 14. SHOW TEMPERED WATER IS BRING SUPPLIED TO ALL TOILET |
| | ROOM SINK BY A ASSE 1070 APPROVED DEVICE. FBC-P 416.5, |
| | 607.1.2 |
| | |
| | |
| | |
| | 15. PROVIDE MIN FIXTURE SUPPLY SCHEDULED SHOWING MIN |
| | REQUIRED UNDER FBC-P 403.1 AND FIXTURES BEING SUPPLIED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |