Plan Review Notes
Plan Review Notes For Permit 19051456
Permit Number 19051456
Review Stop B
Sequence Number 2
Notes
Date Text
2019-10-29 10:13:162017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051456
 ADD: 2711 EXCHANGE COURT
 CONT: TBD/ TO BE DETERMINED
 TEL: 786-488-4714
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT. 29/2019
 ACTION: DENIED
  
 NOTE: NEW DESIGNER OF RECORD.
 1) IN THE ARCHITECTS TITLEBLOCK WITHIN THE SEAL IT
 APPEARS THE ARCHITECT HAS USED A RUBBER STAMP
 SIGNATURE, NOT AN ORIGINAL SINCE THEY ARE EXACTLY THE
 SAME ON EACH SHEET. DEFINITION OF SIGNATURE: A
 SIGNATURE IS A HANDWRITTEN (AND OFTEN STYLIZED)
 DEPICTION OF SOMEONE'S NAME OR EVEN A SIMPLE "X" OR
 OTHER MARK THAT A PERSON WRITES ON DOCUMENTS AS A PROOF
 OF IDENTITY AND INTENT. FLORIDA STATUTE 481 REQUIRES A
 SIGNATURE (HANDWRITTEN).
 F. S. 481.221(4) NO REGISTERED ARCHITECT SHALL AFFIX,
 OR PERMIT TO BE AFFIXED, HER OR HIS SEAL OR SIGNATURE
 TO ANY FINAL CONSTRUCTION DOCUMENT OR INSTRUMENT OF
 SERVICE WHICH INCLUDES ANY PLAN, SPECIFICATION,
 DRAWING, OR OTHER DOCUMENT WHICH DEPICTS WORK WHICH SHE
 OR HE IS NOT COMPETENT TO PERFORM.
  
 2) THE COVERSHEET LIST FOR SUITE: A AN EDUCATIONAL
 OCCUPANCY. INDICATE THE USAGE?
  
 2A)(1) THE MAJOR PORTION OF THE SQUARE FOOTAGE OF THIS
 TENANT SPACE 2584 SQ. FT. AS OPEN GYM. PLEASE PROVIDE
 WHAT AGE GROUP ARE USING THIS FACILITY. IS THIS GYM
 ASSOCIATED WITH A SCHOOL?
 2017 FBC-B SECTION 305.1 EDUCATIONAL GROUP E.
 EDUCATIONAL GROUP E OCCUPANCY INCLUDES, AMONG OTHERS,
 THE USE OF A BUILDING OR STRUCTURE, OR A PORTION
 THEREOF, BY SIX OR MORE PERSONS AT ANY ONE TIME FOR
 EDUCATIONAL PURPOSES THROUGH THE 12TH GRADE.
  
 2A)(2) THE OPEN GYM WITH A SQUARE FOOTAGE OF 2584 SQ.
 FEET AS INDICATED ON THE COVERSHEET ALSO STATES AN
 OCCUPANT LOAD FACTOR OF 20 NET. THIS OCCUPANT LOAD
 FACTOR IS TAKEN FOR A CLASSROOM SETTING WITH DESK AND
 CHAIRS. PLEASE REVIEW IN THE 2017 FBC-B TABLE 1004.1.2
 FOR EXERCISE ROOMS AN OCCUPANT LOAD FACTOR OF 50 GROSS
 SHOULD BE TAKEN.
  
 2A)(3) TO TAKE THE OCCUPANT LOAD FACTOR FOR A GYM YOU
 WILL NEED TO PROVIDE AN EQUIPMENT LAYOUT OF THE
 EQUIPMENT. TABLE 1004.1.2.
  
 2A)(4) PLEASE ALSO REVIEW THE REQUIREMENTS UNDER THE
 2017 FBC-ACCESSIBILITY CODE FOR EXERCISE MACHINES AND
 EQUIPMENT SECTION 1004.1 CLEAR FLOOR SPACE. EXERCISE
 MACHINES AND EQUIPMENT SHALL HAVE A CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR TRANSFER OR FOR USE
 BY AN INDIVIDUAL SEATED IN A WHEELCHAIR. CLEAR FLOOR OR
 GROUND SPACES REQUIRED AT EXERCISE MACHINES AND
 EQUIPMENT SHALL BE PERMITTED TO OVERLAP.
  
 2B) IS THIS TENANT SPACE GOING TO BE USED AS A DAYCARE?
 2017 FBC-B SECTION 305.2 GROUP E, DAY CARE FACILITIES.
 THIS GROUP INCLUDES BUILDINGS AND STRUCTURES OR
 PORTIONS THEREOF OCCUPIED BY MORE THAN FIVE CHILDREN
 OLDER THAN 21/2 YEARS OF AGE WHO RECEIVE EDUCATIONAL,
 SUPERVISION OR PERSONAL CARE SERVICES FOR FEWER THAN 24
 HOURS PER DAY.
  
 2C) THE COVERSHEET ALSO LIST OFFICE/ VOCATIONAL
 TRAINING WITH1623 SQUARE FEET, AN AND OCCUPANT LOAD
 FACTOR OF 50 NET. PLEASE PROVIDE ADDITIONAL INFORMATION
 AS TO WHAT AGE GROUP WILL BE ATTENDING AND RECEIVING
 VOCATIONAL TRAINING? SEE THE 2017 FBC-B SECTION:
 304.1 BUSINESS GROUP B OCCUPANCIES INCLUDE : TRAINING
 AND SKILL DEVELOPMENT NOT IN A SCHOOL OR ACADEMIC
 PROGRAM (THIS SHALL INCLUDE, BUT NOT BE LIMITED TO,
 TUTORING CENTERS, MARTIAL ARTS STUDIOS, GYMNASTICS AND
 SIMILAR USES REGARDLESS OF THE AGES SERVED, AND WHERE
 NOT CLASSIFIED AS A GROUP A OCCUPANCY.
  
 3) SHEET A-2 THE FLOOR PLAN FOR SUITES A & B AND A4
 RESTROOM ELEVATIONS ARE ALL WRONG FOR ACCESSIBILITY TO
 THE WATERCLOSET FOR AN ACCESSIBLE RESTROOM. PLEASE
 REVIEW THE 2017 ACCESSIBILITY CODE SECTIONS:
  
 3A) WATER CLOSET. 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 3B) 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
  
 3C) THE REAR WALL OF THE RESTROOM SHOWS THE REAR GRAB
 BAR BUT THERE ARE NO HORIZONTAL DIMENSIONS SHOWING
 COMPLIANCE WITH:
 2017 ACCESSIBILITY CODE 604.5.2 REAR WALL. THE REAR
 WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 INCHES (610
 MM) MINIMUM ON THE OTHER SIDE.
  
 3D) THE SINKS WILL ALSO NEED TO SHOW COMPLIANCE WITH:
 2017 ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER LAVATORIES AND SINKS.
  
 4) SHEET A2 NEW OFFICE # 6 SHOW A NEW GLAZED WINDOW
 WITHIN 2 FEET OF THE DOOR. PLEASE SHOW COMPLIANCE WITH
 2406.4.2 GLAZING ADJACENT TO DOORS. GLAZING IN AN
 INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT TO A DOOR
 WHERE THE NEAREST VERTICAL EDGE OF THE GLAZING IS
 WITHIN A 24-INCH (610 MM) ARC OF EITHER VERTICAL EDGE
 OF THE DOOR IN A CLOSED POSITION AND WHERE THE BOTTOM
 EXPOSED EDGE OF THE GLAZING IS LESS THAN 60 INCHES
 (1524 MM) ABOVE THE WALKING SURFACE SHALL BE CONSIDERED
 A HAZARDOUS LOCATION.
  
 5A) SHEET A2 SHOWS A LUNCHROOM / CAFETERIA. THERE ARE
 NO ELEVATIONS FOR THIS ROOM COMPLIANCE CAN NOT BE
 REVIEWED FOR: 2017 ACCESSIBILITY CODE SECTION 2017
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. LAVATORIES
 AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 5B) 2017 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR
 SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305,
 POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 EXCEPTIONS: 1.A PARALLEL APPROACH COMPLYING WITH 305
 SHALL BE PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE
 A COOK TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND
 TO WET BARS.
  
 6) SHEET A2 SHOWS A LUNCHROOM / CAFETERIA. THERE IS NO
 FURNITURE PLAN FOR THIS ROOM COMPLIANCE CANNOT BE
 REVIEWED FOR: 2017 ACCESSIBILITY CODE SECTIONS:
  
 6A ) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 6A)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6A)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7) ARE ALL OF THE EXITS LEVEL WITH THE EXTERIOR GRADE,
 NOT SHOWN ON THE PLANS? 2017 ACCESS. CODE 206.4.1
 PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES REQUIRED BY
 206.4.2 THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL
 PUBLIC ENTRANCES SHALL COMPLY WITH 404.
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 8) AT THIS TIME A OCCUPANCY CANNOT BE DETERMINED, FOR
 DAYCARE AND EDUCATIONAL OCCUPANCIES CHAPTER 4 OF THE
 FBC-B 2017 HAS SEPARATE REQUIREMENTS FOR THESE
 OCCUPANCIES:
 DAYCARE OCCUPANCIES SECTION 466
 SCHOOLS: KINDERGARTEN THROUGH THE 12 GRADE SECTION 468.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  