2019-07-02 11:09:39PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE OCCUPANCY AND OCCUPANT LOAD FOR EACH SPACE.
 FBC 107.3.5
  
 2) BEING THAT THIS WILL BE 2 SEPARATE SPACES THE
 PLUMBING CODE 403.1, 410.3 REQUIRE BOTH A MOP SINK AND
 HI-LOW DRINKING FOUNTAIN FOR EACH SPACE.
  
 3) PROVIDE CLEAR FLOOR AND TURNING SPACE FOR ALL TOILET
 ROOMS. FBC-ACC 603.2.1, 304
  
 4) PROVIDE CLEAR FLOOR AND TURNING SPACE WITH DETAIL OF
 CABINET HEIGHT SHOWING MAX 34" FOR THE BREAK ROOM SINK
 IS TO REMAIN COMPLIANT AS DESIGNED AND INSTALLED UNDER
 PERMIT # 03070117. FBC 107.2.1
  
 5) TOILET ROOM NEAR BREAKROOM EXISTING AND NEW PLAN IS
 NOT PER CITY RECORDS (#03070117) AND FBC-ACC 604.8.1.7
 REQUIRES THE TOILET TO BE DIAGONAL TO THE DOOR.
  
 6) LABEL EACH TOILET ROOM AS MEN'S AND WOMEN'S SHOWING
 YOU ARE PROVIDING SEPARATE FACILITIES FOR EACH. FBC-P
 403.2
  
 7) PROVIDE ROOM MEASUREMENTS ON PLANS. FBC 107.3.5
  
 8) PROVIDE LOCATION AND INSTALLATION MANUAL OF WATER
 HEATER. SHOW TOTAL DEVELOP LENGTH OF HOT WATER LINE
 FROM THE WATER HEATER TO THE MOST REMOTE OUTLET. PLEASE
 NOTE MUST BE WITH IN 50' OR HAVE A HOT WATER RETURN
 SYSTEM AND ALL HOT WATER PIPING SHALL BE INSULATED.
 FBC-P 607.2, 607.5
  
 9) SHOW TEMPERED WATER IS BRING SUPPLIED TO ALL TOILET
 ROOM SINK BY A ASSE 1070 APPROVED DEVICE. FBC-P 416.5,
 607.1.2
  
 10) PROVIDE A COMPLETED RISER ISOMETRIC FOR BOTH THE
 SANITARY AND WATER SUPPLY SYSTEM. FBC 107.3.5
  
 11) SHT. P1 DETAIL #2 SHOW GRAB BAR BEING MOUNTED 12"
 FROM CENTERLINE OF TOILET. FBCC-ACC 604.5.2
  
 12) PROVIDE MIN FIXTURE SUPPLY SCHEDULED SHOWING MIN
 REQUIRED UNDER FBC-P 403.1 AND FIXTURES BEING SUPPLIED.
  
 13) SHT. P1 SHOW MIRROR AS MAX 40" TO THE REFLECTING
 SURFACE AND NOT TO THE BOTTOM FRAME. FBC-ACC 603.3
  
 14) SHT. P1 CALLS FOR FIXTURES TO BE REPLACED IN SAME
 LOCATION. BEING THIS IS A CHANGE OF USE AND RELOCATION
 OF THE FIXTURE'S THE TOILET ROOMS WILL BE REQUIRED TO
 COMPLY WITH 2017 6TH ED OF THE FLORIDA ACCESSIBILITY
 CODE. PLEASE REMOVE NOTE ON PLAN AS IT MAY MIS-LEAD
 FIELD INSPECTOR. FBC 107.2.1
  
  