| 2019-07-02 11:09:39 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | 1) PROVIDE OCCUPANCY AND OCCUPANT LOAD FOR EACH SPACE. |
| | FBC 107.3.5 |
| | |
| | 2) BEING THAT THIS WILL BE 2 SEPARATE SPACES THE |
| | PLUMBING CODE 403.1, 410.3 REQUIRE BOTH A MOP SINK AND |
| | HI-LOW DRINKING FOUNTAIN FOR EACH SPACE. |
| | |
| | 3) PROVIDE CLEAR FLOOR AND TURNING SPACE FOR ALL TOILET |
| | ROOMS. FBC-ACC 603.2.1, 304 |
| | |
| | 4) PROVIDE CLEAR FLOOR AND TURNING SPACE WITH DETAIL OF |
| | CABINET HEIGHT SHOWING MAX 34" FOR THE BREAK ROOM SINK |
| | IS TO REMAIN COMPLIANT AS DESIGNED AND INSTALLED UNDER |
| | PERMIT # 03070117. FBC 107.2.1 |
| | |
| | 5) TOILET ROOM NEAR BREAKROOM EXISTING AND NEW PLAN IS |
| | NOT PER CITY RECORDS (#03070117) AND FBC-ACC 604.8.1.7 |
| | REQUIRES THE TOILET TO BE DIAGONAL TO THE DOOR. |
| | |
| | 6) LABEL EACH TOILET ROOM AS MEN'S AND WOMEN'S SHOWING |
| | YOU ARE PROVIDING SEPARATE FACILITIES FOR EACH. FBC-P |
| | 403.2 |
| | |
| | 7) PROVIDE ROOM MEASUREMENTS ON PLANS. FBC 107.3.5 |
| | |
| | 8) PROVIDE LOCATION AND INSTALLATION MANUAL OF WATER |
| | HEATER. SHOW TOTAL DEVELOP LENGTH OF HOT WATER LINE |
| | FROM THE WATER HEATER TO THE MOST REMOTE OUTLET. PLEASE |
| | NOTE MUST BE WITH IN 50' OR HAVE A HOT WATER RETURN |
| | SYSTEM AND ALL HOT WATER PIPING SHALL BE INSULATED. |
| | FBC-P 607.2, 607.5 |
| | |
| | 9) SHOW TEMPERED WATER IS BRING SUPPLIED TO ALL TOILET |
| | ROOM SINK BY A ASSE 1070 APPROVED DEVICE. FBC-P 416.5, |
| | 607.1.2 |
| | |
| | 10) PROVIDE A COMPLETED RISER ISOMETRIC FOR BOTH THE |
| | SANITARY AND WATER SUPPLY SYSTEM. FBC 107.3.5 |
| | |
| | 11) SHT. P1 DETAIL #2 SHOW GRAB BAR BEING MOUNTED 12" |
| | FROM CENTERLINE OF TOILET. FBCC-ACC 604.5.2 |
| | |
| | 12) PROVIDE MIN FIXTURE SUPPLY SCHEDULED SHOWING MIN |
| | REQUIRED UNDER FBC-P 403.1 AND FIXTURES BEING SUPPLIED. |
| | |
| | 13) SHT. P1 SHOW MIRROR AS MAX 40" TO THE REFLECTING |
| | SURFACE AND NOT TO THE BOTTOM FRAME. FBC-ACC 603.3 |
| | |
| | 14) SHT. P1 CALLS FOR FIXTURES TO BE REPLACED IN SAME |
| | LOCATION. BEING THIS IS A CHANGE OF USE AND RELOCATION |
| | OF THE FIXTURE'S THE TOILET ROOMS WILL BE REQUIRED TO |
| | COMPLY WITH 2017 6TH ED OF THE FLORIDA ACCESSIBILITY |
| | CODE. PLEASE REMOVE NOTE ON PLAN AS IT MAY MIS-LEAD |
| | FIELD INSPECTOR. FBC 107.2.1 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | BUILDING DIVISION |
| | CITY OF WEST PALM BEACH |