| Date |
Text |
| 2019-06-03 14:34:18 | 6/3/19 |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET FLOOR PLAN - THERE IS AN INDICATION OF A NEW 2 |
| | HR FIRE RATED DEMISING WALL; HOWEVER, THERE IS NO |
| | LISTED DESIGN CALL OUT. |
| | |
| | PLEASE PROVIDE A LISTED 2 HR FIRE RATING WALL DESIGN. |
| | |
| | |
| | |
| | 1A) SHEET FLOOR PLAN - THERE IS AN INDICATION OF A NEW |
| | 1 HR FIRE RATED DEMISING WALL; HOWEVER, THERE IS NO |
| | LISTED DESIGN CALL OUT. |
| | |
| | PLEASE PROVIDE A LISTED 1 HR FIRE RATING WALL DESIGN. |
| | |
| | |
| | |
| | 2) SHEET FLOOR PLAN - THERE ARE NO INDICATIONS OF THE |
| | WALLS SEPARATING THE BATHROOMS ARE 2 HR FIRE RATED. |
| | |
| | PLEASE PROVIDE DETAILS OF CONTINUES FIRE SEPARATED WALL |
| | RATINGS. |
| | |
| | |
| | |
| | |
| | 2A) SHEET FLOOR PLAN - THERE ARE NO INDICATIONS OF THE |
| | WALL SEPARATING THE OFFICE CAFETERIA AND BATHROOM IS 1 |
| | HR FIRE RATED. |
| | |
| | PLEASE PROVIDE DETAILS OF CONTINUES FIRE SEPARATED WALL |
| | RATINGS. |
| | |
| | |
| | |
| | |
| | 3) NO SHEET - THERE ARE DOORS INDICATED WITHIN THE 2 HR |
| | FIRE RATED WALLS; HOWEVER, THERE IS NO DOOR SCHEDULE |
| | SHOWING APPLICABLE RATING. |
| | |
| | PLEASE PROVIDE RATED DOORS AND A DOOR SCHEDULE, |
| | INCLUDING HARDWARE. |
| | |
| | |
| | |
| | 4) NO SHEET - THERE ARE NUMEROUS DOORS LOCATED |
| | THROUGHOUT THE PROJECT; HOEVER THERE IS NO DOOR |
| | SCHEDULE . |
| | |
| | PLEASE PROVIDE A DOOR SCHEDULE FOR EACH DOOR AND |
| | INCLUDE HARDWARE. |
| | |
| | |
| | |
| | 5) SHEET FLOOR PLAN - THERE IS ONLY ONE EXIT FROM LEFT |
| | HAND SUITE AND THE OTHER SUITE THERE ARE NO INDICATION |
| | OF TRAVEL DISTANCE NOR COMMON PATH OF TRAVEL TO THE |
| | EXIT. |
| | |
| | PER NFPA 101, CH |
| | |
| | 38.2.4 NUMBER OF MEANS OF EGRESS. |
| | 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING, EXCEPT |
| | AS OTHERWISE PERMITTED BY 38.2.4.2 THROUGH 38.2.4.6: |
| | (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 7.4. |
| | (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| | ON EVERY STORY. |
| | (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| | ACCESSIBLE FROM EVERY |
| | PART OF EVERY STORY. |
| | 38.2.4.2 EXIT ACCESS, AS REQUIRED BY 38.2.4.1(3), SHALL |
| | BE PERMITTED TO |
| | INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES |
| | PERMITTED AS COMMON |
| | PATHS OF TRAVEL BY 38.2.5.3. |
| | 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR |
| | AREA WITH A TOTAL |
| | OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT |
| | THE LEVEL OF EXIT |
| | DISCHARGE FOR THE BUILDING. |
| | (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT, |
| | INCLUDING TRAVEL WITHIN |
| | THE EXIT, SHALL NOT EXCEED 100 FT (30 M). |
| | (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN |
| | 38.2.4.3(2) SHALL BE ON THE |
| | SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY, |
| | SUCH STAIRS SHALL |
| | NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE |
| | FOLLOWING |
| | ALSO SHALL APPLY: |
| | (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE |
| | ENCLOSURES TO |
| | SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH |
| | NO |
| | DOOR OPENINGS THEREIN. |
| | (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2 |
| | SHALL BE |
| | PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15 |
| | FT (4570 |
| | MM) VERTICAL TRAVEL LIMITATION. |
| | |
| | PLEASE PROVIDE A LIFE SAFETY SHEET WITH DIMENSIONS |
| | SHOWING COMPLIANCE WITH THE ABOVE. |
| | |
| | |
| | 6) SHEET FLOOR PLAN - AN EXIT SIGN IS INDICATED WITHIN |
| | THE NEW LOBBY AREA AT THE DOOR LEADING TO THE ADJACENT |
| | SUITE. |
| | |
| | AN EXIT CAN NOT PASS THRU AND ADJACENT OCCUPANCY. |
| | |
| | PER NFPA 101, CH 7 |
| | |
| | 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE |
| | PERMITTED TO BE |
| | THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS, |
| | PROVIDED THAT SUCH |
| | ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED. |
| | FOYERS, LOBBIES, AND |
| | RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS |
| | SHALL NOT BE |
| | CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE |
| | ARRANGED SO |
| | THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA |
| | IDENTIFIED UNDER |
| | PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43. |
| | 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND |
| | 7.2.1.5. |
| | 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH |
| | KITCHENS, |
| | STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND |
| | 37, |
| | RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR |
| | OTHER ROOMS OR |
| | SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH |
| | ROOMS OR |
| | SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18, |
| | 19, 22, OR 23. |
| | |
| | THERE WOULD BE NO WAY OF KNOWING THAT THE ADJACENT |
| | OCCUPANCY IS OPEN NOR IF THE SOLE EXIT DOOR IS |
| | UNLOCKED. |
| | |
| | THIS DOOR CAN NOT BE AN EXIT. |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |