Plan Review Notes
Plan Review Notes For Permit 19051456
Permit Number 19051456
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-03 14:34:186/3/19
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FLOOR PLAN - THERE IS AN INDICATION OF A NEW 2
 HR FIRE RATED DEMISING WALL; HOWEVER, THERE IS NO
 LISTED DESIGN CALL OUT.
  
 PLEASE PROVIDE A LISTED 2 HR FIRE RATING WALL DESIGN.
  
  
  
 1A) SHEET FLOOR PLAN - THERE IS AN INDICATION OF A NEW
 1 HR FIRE RATED DEMISING WALL; HOWEVER, THERE IS NO
 LISTED DESIGN CALL OUT.
  
 PLEASE PROVIDE A LISTED 1 HR FIRE RATING WALL DESIGN.
  
  
  
 2) SHEET FLOOR PLAN - THERE ARE NO INDICATIONS OF THE
 WALLS SEPARATING THE BATHROOMS ARE 2 HR FIRE RATED.
  
 PLEASE PROVIDE DETAILS OF CONTINUES FIRE SEPARATED WALL
 RATINGS.
  
  
  
  
 2A) SHEET FLOOR PLAN - THERE ARE NO INDICATIONS OF THE
 WALL SEPARATING THE OFFICE CAFETERIA AND BATHROOM IS 1
 HR FIRE RATED.
  
 PLEASE PROVIDE DETAILS OF CONTINUES FIRE SEPARATED WALL
 RATINGS.
  
  
  
  
 3) NO SHEET - THERE ARE DOORS INDICATED WITHIN THE 2 HR
 FIRE RATED WALLS; HOWEVER, THERE IS NO DOOR SCHEDULE
 SHOWING APPLICABLE RATING.
  
 PLEASE PROVIDE RATED DOORS AND A DOOR SCHEDULE,
 INCLUDING HARDWARE.
  
  
  
 4) NO SHEET - THERE ARE NUMEROUS DOORS LOCATED
 THROUGHOUT THE PROJECT; HOEVER THERE IS NO DOOR
 SCHEDULE .
  
 PLEASE PROVIDE A DOOR SCHEDULE FOR EACH DOOR AND
 INCLUDE HARDWARE.
  
  
  
 5) SHEET FLOOR PLAN - THERE IS ONLY ONE EXIT FROM LEFT
 HAND SUITE AND THE OTHER SUITE THERE ARE NO INDICATION
 OF TRAVEL DISTANCE NOR COMMON PATH OF TRAVEL TO THE
 EXIT.
  
 PER NFPA 101, CH
  
 38.2.4 NUMBER OF MEANS OF EGRESS.
 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING, EXCEPT
 AS OTHERWISE PERMITTED BY 38.2.4.2 THROUGH 38.2.4.6:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM EVERY
 PART OF EVERY STORY.
 38.2.4.2 EXIT ACCESS, AS REQUIRED BY 38.2.4.1(3), SHALL
 BE PERMITTED TO
 INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS COMMON
 PATHS OF TRAVEL BY 38.2.5.3.
 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR
 AREA WITH A TOTAL
 OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT
 THE LEVEL OF EXIT
 DISCHARGE FOR THE BUILDING.
 (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT,
 INCLUDING TRAVEL WITHIN
 THE EXIT, SHALL NOT EXCEED 100 FT (30 M).
 (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN
 38.2.4.3(2) SHALL BE ON THE
 SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY,
 SUCH STAIRS SHALL
 NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE
 FOLLOWING
 ALSO SHALL APPLY:
 (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE
 ENCLOSURES TO
 SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH
 NO
 DOOR OPENINGS THEREIN.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE
 PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15
 FT (4570
 MM) VERTICAL TRAVEL LIMITATION.
  
 PLEASE PROVIDE A LIFE SAFETY SHEET WITH DIMENSIONS
 SHOWING COMPLIANCE WITH THE ABOVE.
  
  
 6) SHEET FLOOR PLAN - AN EXIT SIGN IS INDICATED WITHIN
 THE NEW LOBBY AREA AT THE DOOR LEADING TO THE ADJACENT
 SUITE.
  
 AN EXIT CAN NOT PASS THRU AND ADJACENT OCCUPANCY.
  
 PER NFPA 101, CH 7
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
 THERE WOULD BE NO WAY OF KNOWING THAT THE ADJACENT
 OCCUPANCY IS OPEN NOR IF THE SOLE EXIT DOOR IS
 UNLOCKED.
  
 THIS DOOR CAN NOT BE AN EXIT.
  
 PLEASE CORRECT.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  