| 2019-07-08 08:08:14 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19051456 |
| | ADD: 2711 EXCHANGE COURT |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 786-488-4714 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 09/2019 |
| | ACTION: DENIED |
| | |
| | 1) FIRE SAFETY FLOOR PLAN MISSING INFORMATION: |
| | 1A) THE COVERSHEET & LIFE SAFETY/ FIRE SAFETY FLOOR |
| | PLAN INDICATE THE PLANS WERE DESIGNED TO THE 2017 |
| | EXISTING BUILDING CODE & BUILDING CODE. WHAT THE PLANS |
| | ARE MISSING AS UNDER THE 2017 EXISTING BUILDING CODE |
| | WHAT METHOD LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 |
| | DID THE DESIGNER OF RECORD USE? |
| | |
| | 1B) ON THE COVERSHEET UNDER THE HEADING CODE |
| | INFORMATION THE PLANS STATE THE PLANS WERE ALSO |
| | DESIGNED TO PALM BEACH COUNTY LOCAL AMENDMENTS. PLEASE |
| | BE AWARE THIS PROJECT IS LOCATED IN THE CITY LIMITS OF |
| | WEST PALM BEACH, FLORIDA AND SUBJECT TO THE 2017 WEST |
| | PALM BEACH AMENDMENTS (CHAPTER 1 ADMINISTRATION) TO THE |
| | FLORIDA BUILDING CODE, NOT THE COUNTY AMENDMENTS. |
| | PLEASE UPDATE PLANS. |
| | |
| | 1C) THE 2017 WEST PALM BEACH AMENDMENTS (CHAPTER 1 |
| | ADMINISTRATION)TO THE FLORIDA BUILDING CODE |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1. BUILDING. |
| | OCCUPANCY TYPE |
| | MINIMUM TYPE OF CONSTRUCTION |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | FIRE SPRINKLERED OR NOT / REQUIRED? |
| | |
| | 1D) NEITHER THE COVERSHEET NOR THE LIFE SAFETY/ FIRE |
| | SAFETY FLOOR PLAN INDICATE TO WHAT SCALE THE PLANS WERE |
| | DRAWN TOO? 107.2.1.3 QUALITY OF BUILDING PLANS. |
| | BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 |
| | INCH SCALE. |
| | |
| | 1E) THE DESIGNER OF RECORD LIST ON THE LIFE SAFETY/ |
| | FIRE SAFETY FLOOR PLAN INDICATES THE DEMISING WALL IS |
| | TO BE A 2 HOUR FIRE RATED WALL A DESCRIPTION OF THE |
| | COMPONENTS IS GIVEN BUT NOT THE LISTING OF THE ASSEMBLY |
| | NOR THE SIZE AND SPACING FOR THE FASTENERS. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | 2017 FBC-B SECTION 708.3 & 708.4. FIRE PARTITIONS AND |
| | CONTINUITY. |
| | |
| | 1F) THERE ARE 2 NOTES DEALING WITH JOINTS AND OR |
| | OPENINGS WITHIN THE 2 HOUR FIRE RATED WALL. 1ST) |
| | PROVIDE FIRER RETARDANT FOAM CAULKING FOR AREAS, THE |
| | 2ND) USE FIRE RETARDANT COMPOUND TO SEAL ANY OPENINGS |
| | IN THE FIRE RATED WALL. |
| | 2017 FBC-B 715.1. JOINTS INSTALLED IN OR BETWEEN |
| | FIRE-RESISTANCE-RATED WALLS, SHALL BE PROTECTED BY AN |
| | APPROVED FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST |
| | THE PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE |
| | REQUIRED FIRE-RESISTANCE RATING OF THE WALL BETWEEN |
| | WHICH THE SYSTEM IS INSTALLED. FIRE-RESISTANT JOINT |
| | SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH SECTION |
| | 715.3. PLEASE PROVIDE DOCUMENTATION OF APPROVAL. IF |
| | THIS IS TO LEFT TO THE CONTRACTOR THEN THE SYSTEM WILL |
| | NEED TO HAVE THE DESIGNER OF RECORD APPROVAL (SHOP |
| | DRAWING STAMP OF APPROVAL) BEFORE BEING SUBMITTED TO |
| | THE BUILDING DEPARTMENT BEFORE THE INSTALLATION OF THE |
| | PRODUCT. THE FIRE-RESISTANT JOINT SYSTEMS SHALL BE |
| | TESTED IN ACCORDANCE WITH SECTION 715.3. |
| | |
| | 1G) THE PLANS INDICATE A 2 HOUR TENANT SEPARATION WALL |
| | IS TO BE INSTALLED BUT THE WALL DOES NOT INDICATE A 2 |
| | HOUR RATING FROM EXTERIOR WALL TO THE OPPOSITE EXTERIOR |
| | WALL. THE FOYER IS IN QUESTION IT COULD BE A COMMON |
| | ELEMENT TO BOTH TENANTS? THE OTHER ISSUE IS WHEN YOU |
| | GET INTO THE RESTROOMS THERE ARE NO NEW WALLS SHOWN OR |
| | FIRE RATING. THE SAME SYMBOL IS USED FOR NEW WALLS AND |
| | THE 2 HOUR FIRE RATED WALLS. |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1H) WITHIN THIS SET OF PLANS THERE IS NO DOOR |
| | IDENTIFICATION TAGS OR DOOR SCHEDULE TO SHOW COMPLIANCE |
| | WITH SECTION 1010.1.1. SIZE OF DOORS OF THE 2017 FBC-B. |
| | |
| | 1I) IN THE 2 HOUR FIRE RATED WALL THERE IS AT LEAST ONE |
| | DOOR OPENING THAT WOULD NEED TO HAVE A FIRE RATING |
| | COMPLYING WITH 2017 FBC-B TABLE 716.5. |
| | |
| | THE FLOOR PLAN DOES NOT INDICATE THE OCCUPANT LOAD FOR |
| | OFFICE A. BUT THE OFFICE A IS OVER 5,000 SQ. FT. |
| | REQUIRING 2 EXITS. PLEASE SHOW THE ACCESSIBLE 2 |
| | REQUIRED EXITS. |
| | |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | THE GOOGLE MAPS SHOWS THE FRONT ENTRY WITH A RAMP BUT |
| | NO TOP LANDING, PLEASE PROVIDE THE RISE AND RUN OF THE |
| | EXISTING RAMP TO SEE IF THIS IS A CODE COMPLIANT RAMP. |
| | THERE ARE 2 OTHER EXITS SHOWN ON THE PLANS BUT NEITHER |
| | OF THESE EXITS HAVE A RAMP EGRESS COMPONENT. |
| | |
| | 1J) THE VALUE OF THIS PROJECT IS INDICATED AS |
| | $80,000.00 DOLLARS IN VALUE. PLEASE SHOW WHERE UP TO |
| | 20% ($16,000.00) OF THIS VALUE WILL BE USED IN |
| | ACCESSIBLE UPGRADES TO THE PROJECT AND AS IN ORDER AS |
| | LISTED |
| | BELOW. EITHER THE DESIGNER OF RECORD OR THE CONTRACTOR |
| | WILL NEED TO SUBMIT ON THEIR LETTERHEAD WHERE THE FUNDS |
| | WILL BE SPENT. |
| | 2017 FBC-ACCESSIBILITY CODE. 202.4.2 ACCESSIBLE |
| | FEATURES IN THE EVENT OF DISPROPORTIONALITY. |
| | |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | 1K) THE FLOOR PLAN INDICATES THE OFFICE CAFETERIA IS |
| | EXISTING COMPLIANCE WITH AN ACCESSIBLE SINK CANNOT BE |
| | DETERMINED NOR IF THERE IS A MICROWAVE BUILT INTO THE |
| | UPPER CABINETS? |
| | SINKS. 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 |
| | HEIGHT. SINKS SHALL BE INSTALLED WITH THE FRONT OF THE |
| | HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1 |
| | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| | OBSTRUCTED HIGH REACH. |
| | |
| | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL |
| | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL |
| | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| | MAXIMUM. |
| | |
| | 2) THE ACCESSIBLE RESTROOMS ARE NOT SHOWN ON THE LIFE |
| | SAFETY/ FIRE FLOOR PLAN BUT IN THE PLUMBING SHEET P1. |
| | 2A) PLEASE NOTE THE GRAB BARS FOR THE WATER CLOSET ARE |
| | SHOWN TO BE MEASURED FROM THE FINISH FLOOR TO THE |
| | CENTER OF THE GRAB BAR. PLEASE NOTE UNDER THE 2010 |
| | ACCESSIBILITY CODE THE GRAB BARS ARE TO BE MEASURED TO |
| | THE TOP OF THE GRASPABLE SURFACE NOT CENTER LINED. 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB |
| | BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE, NOT CENTERLINE. |
| | |
| | 2B) MIRRORS. 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | |
| | 2C) PLEASE PROVIDE THE DIMENSIONS FOR THE BACKWALL OF |
| | THE ACCESSIBLE RESTROOMS ON THE FLOOR PLAN. IT APPEARS |
| | THAT THE DETAIL # 2 IS CORRECT AS FAR AS A CLEAR |
| | OVERLAP FOR THE WATER CLOSET BUT THE FLOOR PLAN DOES |
| | NOT SHOW COMPLIANCE WITH THE 2017 ACCESS. CODE SECTION |
| | 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| | THE REAR WALL. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |