Plan Review Notes
Plan Review Notes For Permit 19051291
Permit Number 19051291
Review Stop B
Sequence Number 2
Notes
Date Text
2020-02-21 18:28:25RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
 ORIGINAL COMMENT:
 1- ORIGINALS PLANS WERE APPROVED UNDER THE 2014 FBC 5TH
 EDITION NOT THE 2017 FBC 6TH EDITION. NEED TO REVISE
 PLANS ACCORDINGLY TO AVOID CONFLICTS/DELAYS. REVISE
 CODE REFERENCE ON SHEET A1 AND S1 ACCORDINGLY.
 CHAPTER 553 F.S.
  
 RESPONSE:
 ARCHITECTURAL PLANS WERE REVISED TO REFLECT THE 2014
 FBC BUT NEW STRUCTURAL INSULATED PANELS (SIP)
 STRUCTURAL DRAWINGS AND CLARK DIETRICH DRAWINGS ARE
 REFERENCING THE 2017 FBC. REVISE STRUCTURAL DRAWINGS TO
 MATCH CODE EDITION UNDER WHICH ARCHITECTURAL DESIGN
 CRITERIA WAS DONE. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- OK.
  
 3- OK
  
 ORIGINAL COMMENT:
 4- SECOND FLOOR ROOF PLAN ON SHEET A3. SHOW LOCATION OF
 OVERFLOW SCUPPERS SHOWING COMPLIANCE WITH SEC. R903.4.1
 FBC-RESIDENTIAL. NOTE: OVERFLOW SCUPPERS NEED TO BE
 LOCATED CLOSE TO THE VERTICAL LEADER. REVISE OVERFLOW
 SCUPPERS LOCATION SHOWN ON THE NORTH ELEVATION ON SHEET
 A4. THEY NEED TO BE CLOSER TO THE VERTICAL LEADER.
  
 RESPONSE:
 SCUPPERS WERE DELETED. GUTTERS WITH DOWNSPOUTS ARE
 REQUIRED WHEN THE WHEN THE ROOF EAVE IS LESS THAN 6".
 SPECIFY AND SHOW GUTTERS AND DOWNSPOUTS ON PLANS AND
 EXTERIOR ELEVATIONS AS REQUIRED BY SEC. R318.5
 FBC-RESIDENTIAL.
  
  
 5- OK.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) OK.
  
 ORIGINAL COMMENT:
 B)BALCONY FINISH MEMBRANE. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 PRODUCT APPROVAL WAS SUBMITTED IS FOR THE FLAT ROOF
 SYSTEM OVER THE STRUCTURAL INSULATED PANELS (SIP) WITH
 CEMENTITIOUS WOOD FIBER DECK. SEE SIP DRAWINGS AND
 PRODUCT APPROVALS. THE BALCONY SUBSTRATE ARE NOT
 STRUCTURAL INSULATED PANELS. IT IS WOOD. NEED PRODUCT
 APPROVAL FOR THIS APPLICATION.
  
 C) OK.
  
 NEW COMMENTS ON PRODUCT APPROVALS:
 D) FLAT ROOF OVER CEMENTITIOUS WOOD FIBER DECKS NOA
 17-1003.06 SUBMITTED. CLEARLY MARK WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.2.1
 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 FAC 61G20-3.001.
  
 E)PROVIDE COMPLETE PRODUCT APPROVAL (2 COPIES) FOR
 STRUCTURAL INSULATED ROOF PANELS. PRODUCT APPROVAL
 SUBMITTED IS INCOMPLETE. NEED TO PROVIDE COMPLETE
 FLORIDA PRODUCT APPROVAL (2 COPIES), INCLUDING THE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO
 THE DRAWINGS SUBMITTED. THE FLORIDA PRODUCT APPROVAL IS
 REQUIRED BECAUSE IT SHOWS IF PRODUCT IS APPROVED AND
 CURRENT CODE IN EFFECT.
  
 6.1)DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 SUBMITTED AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
  
 7-ENERGY CALCULATIONS SUBMITTED:
  
 ORIGINAL COMMENT:
 A) ORIGINALS PLANS AND ENERGY CALCULATIONS WERE
 APPROVED UNDER THE 2014 FBC 5TH EDITION NOT THE 2017
 FBC 6TH EDITION. NEED TO REVISE ENERGY CALCULATIONS AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B)THE ENERGY FORM IS REQUIRED TO BE CERTIFIED AT THE
 BOTTOM BY THE OWNER OR THE OWNER LEGALLY DESIGNATED
 AGENT AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 OK. IT WAS SIGNED. BUT, SINCE ENERGY CALCULATIONS NEED
 TO BE REVISED AGAIN. THIS IS A REMAINDER. PLEASE MAKE
 SURE REVISED ENERGY CALCULATIONS ARE SIGNED WHEN
 RE-SUBMITTED.
  
  
 ORIGINAL COMMENT:
 C)PAGE 2 OF 5 INDICATES THAT THERE IS A KITCHEN IN THE
 ADDITION. THIS NEEDS TO BE COORDINATED WITH ITEM #2
 ABOVE. IF ZONING DOESN'T ALLOW THE KITCHENETTE, THEN
 ENERGY CALCULATIONS WOULD NEED TO BE REVISED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) NUMBER OF BEDROOMS SHOWN UNDER "SPACES" ON PAGE 2 OF
 5 DOESN'T MATCH NUMBER OF BEDROOMS SHOWN ON PAGE 1 OF 5
 AND ON PLANS. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 E) R-VALUE SHOWN UNDER "CEILING" INFORMATION ON SHEET 2
 OF 5 DOESN'T MATCH R-VALUE SHOWN ON PAGE 1 OF 5 AND ON
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NOTE: SAME ENERGY CALCULATIONS WERE SUBMITTED. THEY
 WERE NOT REVISED. PLANS WERE REVISED AFTER THE ENERGY
 CALCULATIONS WERE DONE. PLEASE REVIEW PLANS BEFORE
 REVISING THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 8- OK.
  
 PLANS WERE COMPLETELY REVISED AFTER LAST REVIEW. THE
 FOLLOWING COMMENTS ARE BASED ON THE NEW INFORMATION
 PROVIDED.
  
 9- REVISED ARCHITECTURAL PLANS SUBMITTED NOW ARE
 MISSING THE ROOF FRAMING PLAN AND SPECIFICATIONS FOR
 THE PROPOSED PATIO ROOF. SEC. R301.2.1 FBC-RESIDENTIAL.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 10- WALLS CONSTRUCTION SHOWN ON FIRST AND SECOND
 ARCHITECTURAL FLOOR PLANS (SHEETS A2 AND A3) AND WALL
 TYPES (SHOWN ON SHEET A2 DON'T MATCH FLOOR PLANS SHOWN
 ON THE STRUCTURAL INSULTED PANELS (SIP) ENGINEERED
 FLOOR PLANS. ALL THE SIP ENGINEERED FLOOR PLANS SHOW
 FURRING WALLS ON THE INTERIOR SIDE OF THE WALL.
 ARCHITECTURAL PLANS DON'T SHOW THIS TYPE OF WALLS.
 REVISE AS REQUIRED TO MATCH. THIS AFFECTS THE
 DIMENSIONS OF THE ROOMS ALSO.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 11- NEW ROOF OVER PROPOSED PATIO ON SHEET A3 SPECIFIES
 1/8 PER FOOT SLOPE. NEED 1/4 PER FOOT SLOPE NOT 1/8 AS
 REQUIRED BY SEC. R905.11.1. REVISE AS REQUIRED.
  
 12- REVISE GARAGE DOOR STRUCTURAL BUCK DETAIL 1/A6. THE
 SUBSTRATE IS NOT CONCRETE BLOCK ANYMORE. THE SUBSTRATE
 IS STRUCTURAL INSULATED PANEL (SIP). NOTE: DETAIL SHOWN
 SHOW FASTENERS TO THE FOAM. STRUCTURAL BUCK NEED TO BE
 SUPPORTED ON THE DOOR JAMB TO RESIST THE WIND LOADS.
 REVISE AS REQUIRED. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 13- ARCHITECTURAL PLANS SPECIFY PLYWOOD FACE SHEET ON
 THE EXTERIOR SIDE OF THE STRUCTURAL INSULATED ROOF
 PANELS (SIP). SIP PLANS AND PRODUCT APPROVAL SUBMITTED
 SPECIFY MGO FACE SHEETS. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 14- STRUCTURAL INSULTED PANELS (SIP) ENGINEERED FLOOR
 PLANS SUBMITTED:
 A) PLANS NEED TO BE DESIGNED BASED ON THE SAME CODE
 USED ON THE ARCHITECTURAL DRAWINGS. FBC- 2014 NOT FBC
 2017. NEED TO REVISE PLANS ACCORDINGLY TO AVOID
 CONFLICTS/DELAYS. REVISE AS REQUIRED. CHAPTER 553 F.S.
  
 B) DRAWINGS ARE NOT LEGIBLE. SOME LAYERS ON THE
 DRAWINGS ARE TOO LIGHT AND THEY ARE NOT READABLE.
 PLEASE PROVIDE DRAWINGS WITH DARK INK SO ALL THE
 INFORMATION IS LEGIBLE. THIS WILL HELP ALSO FOR PROPER
 THE RECORDS RETENTION SCANNING. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 C) ALL DRAWINGS NEED TO BE REVIEWED AND APPROVED IN
 WRITING BY THE ARCHITECT OF RECORD BEFORE SUBMITTAL TO
 THIS OFFICE.. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 15- CLARKDIETRICH ENGINEERING SERVICES DRAWINGS
 SUBMITTED:
 A)PLANS NEED TO BE DESIGNED BASED ON THE SAME CODE USED
 ON THE ARCHITECTURAL DRAWINGS. FBC- 2014 NOT FBC 2017.
 NEED TO REVISE PLANS ACCORDINGLY TO AVOID
 CONFLICTS/DELAYS. REVISE AS REQUIRED. CHAPTER 553 F.S.
  
 B)ALL DRAWINGS AND CALCULATIONS SUBMITTED NEED TO HAVE
 A TITLE BLOCK WITH ALL THE INFORMATION OF THE ENGINEER
 AS REQUIRED BY SEC. 61G15-23.001 FAC.
  
 C) ALL DRAWINGS NEED TO BE REVIEWED AND APPROVED IN
 WRITING BY THE ARCHITECT OF RECORD AND BY THE ENGINEER
 OF THE STRUCTURAL INSULATED PANELS (SIP) AS REQUIRED BY
 NOTE ON SHEET LSF-3.1. SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 16- REVISION FEES APPLIES TO ALL RE-SUBMITTALS. THERE
 ARE 28 NEW DRAWINGS AND 4 NEW PRODUCT APPROVALS
 SUBMITTED. OWES $1,435 ON REVISION FEES FOR THIS
 SUBMITTAL. REVISION FEES WILL APPLY ON NEW
 RE-SUBMITTALS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT