| 2019-06-19 08:37:14 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 30A |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | 1. RE: PLAN SHEET A3; SANITARY PLUMBING RISER DIAGRAM |
| | A. DRY VENT SERVING THE SHOWER ON THE SECOND FLOOR |
| | SHALL RISE VERTICALLY FROM THE HORIZONTAL FIXTURE DRAIN |
| | TO A POINT 6? ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST |
| | FIXTURE ON THAT FLOOR BEFORE OFFSETTING HORIZONTALLY |
| | PER FBC RES P3104.3 AND P3104.4. |
| | B. FIXTURE DRAIN FOR SECOND FLOOR SHOWER SHALL BE |
| | PROVIDED WITH A WATER SEAL TRAP PER FBC RES P3201.6. |
| | C. DRY VENT SERVING THE LAVATORY ON THE SECOND FLOOR |
| | SHALL RISE VERTICALLY TO A POINT 6? ABOVE THE FLOOD |
| | LEVEL RIM OF THE FIXTURE BEFORE OFFSETTING HORIZONTALLY |
| | PER FBC RES P3104.4. |
| | D. THE SANITARY PIPING SERVING THE SECOND FLOOR |
| | BATHROOM SHALL NOT DISCHARGE THOUGH THE FIRST FLOOR |
| | BATHROOM GROUP PER FBC RES P3108.1. |
| | E. DRY VENT SERVING THE TOILET ON THE FIRST FLOOR SHALL |
| | RISE VERTICALLY FROM THE HORIZONTAL FIXTURE DRAIN TO A |
| | POINT 6? ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST |
| | FIXTURE ON THAT FLOOR BEFORE OFFSETTING HORIZONTALLY |
| | PER FBC RES P3104.3 AND P3104.4. |
| | F. THE FIXTURE DRAINS FOR THE SHOWER AND THE FLOOR |
| | DRAIN ON THE FIRST FLOOR SHALL EACH BE PROVIDED WITH A |
| | WATER SEAL TRAP PER FBC RES P3201.6. |
| | G. PROVIDE TRAP SEAL PROTECTION FOR THE FIRST FLOOR |
| | DRAIN PER FBC RES P3201.2.1. SHOW COMPLIANCE USING ONE |
| | OF THE METHODS DESCRIBED IN FBC RES P3201.2.1.1 THROUGH |
| | P3201.2.1.4. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19051291 301 PALMETTO ST |