2019-06-12 18:15:46RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
 1- ORIGINALS PLANS WERE APPROVED UNDER THE 2014 FBC 5TH
 EDITION NOT THE 2017 FBC 6TH EDITION. NEED TO REVISE
 PLANS ACCORDINGLY TO AVOID CONFLICTS/DELAYS. REVISE
 CODE REFERENCE ON SHEET A1 AND S1 ACCORDINGLY.
 CHAPTER 553 F.S.
  
 2- REVISED FLOOR PLANS SHOW A NEW KITCHENETTE. USUALLY,
 ZONING DOESN'T ALLOW SEPARATE COOKING FACILITIES ON A
 SINGLE FAMILY RESIDENCE. THIS NEEDS TO BE COORDINATED
 WITH ZONING. IF ZONING DOESN'T ALLOW A KITCHENETTE,
 THEN THE PLANS NEED TO BE REVISED ACCORDINGLY. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- SHEET S2:
 A) FRAMING FOR NEW BALCONY IS NOT CLEAR. HOW ARE THE
 (2) 2X10 BEAMS ATTACHED TO THE CONCRETE BEAM TB1?. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 B) NEW ROOF HATCH: (1) SPECIFY SIZE. (2) SPECIFY DESIGN
 PRESSURES. (3)PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS FOR NEW ROOF HATCH. SPECIFY ALL FRAMING
 MEMBERS AND CONNECTORS. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 4- SECOND FLOOR ROOF PLAN ON SHEET A3. SHOW LOCATION OF
 OVERFLOW SCUPPERS SHOWING COMPLIANCE WITH SEC. R903.4.1
 FBC-RESIDENTIAL. NOTE: OVERFLOW SCUPPERS NEED TO BE
 LOCATED CLOSE TO THE VERTICAL LEADER. REVISE OVERFLOW
 SCUPPERS LOCATION SHOWN ON THE NORTH ELEVATION ON SHEET
 A4. THEY NEED TO BE CLOSER TO THE VERTICAL LEADER.
  
 5- PROVIDE ICC EVALUATION REPORT (OR ANY OTHER APPROVED
 EVALUATION REPORT)FOR R-20 INSULATION SPECIFIED ON
 PLANS FOR REVISED SECOND FLOOR UNVENTED ATTIC TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. NOTE:
 ARCHITECT OF RECORD TO REVIEW AND APPROVE THE
 EVALUATION REPORT PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)NEW ROOF HATCH AS SHOWN ON PLANS.
  
 B)BALCONY FINISH MEMBRANE. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 C) NEW GARAGE DOOR SIZE THAT MEETS THE DESIGN PRESSURES
 CALCULATED ON SHEET A-4.
  
 7-ENERGY CALCULATIONS SUBMITTED:
 A) ORIGINALS PLANS AND ENERGY CALCULATIONS WERE
 APPROVED UNDER THE 2014 FBC 5TH EDITION NOT THE 2017
 FBC 6TH EDITION. NEED TO REVISE ENERGY CALCULATIONS AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)THE ENERGY FORM IS REQUIRED TO BE CERTIFIED AT THE
 BOTTOM BY THE OWNER OR THE OWNER LEGALLY DESIGNATED
 AGENT AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C)PAGE 2 OF 5 INDICATES THAT THERE IS A KITCHEN IN THE
 ADDITION. THIS NEEDS TO BE COORDINATED WITH ITEM #2
 ABOVE. IF ZONING DOESN'T ALLOW THE KITCHENETTE, THEN
 ENERGY CALCULATIONS WOULD NEED TO BE REVISED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) NUMBER OF BEDROOMS SHOWN UNDER "SPACES" ON PAGE 2 OF
 5 DOESN'T MATCH NUMBER OF BEDROOMS SHOWN ON PAGE 1 OF 5
 AND ON PLANS. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) R-VALUE SHOWN UNDER "CEILING" INFORMATION ON SHEET 2
 OF 5 DOESN'T MATCH R-VALUE SHOWN ON PAGE 1 OF 5 AND ON
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 ****02/24/2020. REVISED THIS COMMENT. I REPEATED THE
 LETTER B TWICE. CHANGED TO LETTER C. (TOTAL ITEMS A TO
 F)
  
 8- ARCHITECT TO PROVIDE NOTES ON DRAWINGS INDICATING
 THAT BALCONY GUARDRAIL SHOP DRAWINGS ARE DEFERRED
 SUBMITTAL AS REQUIRED SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: DEFERRED SUBMITTAL NEED TO BE REVIEWED/APPROVED
 BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THE
 BUILDING DEPARTMENT.
  
  
 REMAINDER:
 ORIGINAL PLANS WERE APPROVED WITH A PROVISO. AS OF NOW,
 INFORMATION REQUESTED ON THE PROVISO HAS NOT BEEN
 SUBMITTED. PLEASE PROVIDE REQUESTED INFORMATION PRIOR
 TO INSPECTIONS TO AVOID CONFLICTS/DELAYS. SEE COPY
 OF-PROVISO BELOW.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE FLAT ROOF RAS 117 CALCULATIONS SUBMITTED:
 (A) APPROVED SYSTEM DOESN'T MATCH SYSTEM SYSTEM
 SUBMITTED WITH NOA 14-0529.02.
 (B)RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED BY
 THE ENGINEER. CHAPTER 471 F.S
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  