2019-05-24 14:03:5205/19/2019 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS
 REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY
 DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION
 MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/
 PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONN
 ECTION-CONTROL-MANUAL FOR MORE INFORMATION. THE 919
 WATTS MODEL IS NOT LEAD-FREE AS THE LF919 IS SO PLEASE
 RESUBMIT SPECS FOR IT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  