| Plan Review Notes For Permit 19051263 |
| Permit Number |
19051263 |
|
| Review Stop |
NFIP |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2019-09-25 14:09:40 | ****PROVISO**** | | | REQUIRED PRIOR TO FIRST INSPECTION | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PLEASE SEE THE ELEVATION CERTIFICATE ON THE FEMA | | | WEBSITE: | | | | | | HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/1520627873824-0 | | | F2350EC4204BCEFF0F01672D86AD151/FF086033_ELEVCERT_FORMO | | | NLY_RE_1MAR2018.PDF | | | | | | FEMA REQUIRES THAT ALL FIELDS ARE COMPLETED. ON THE EC | | | UPLOADED FOR YOUR PROJECT, THERE ARE BLANK LINES (SEE | | | A8, A9). THE BLANK LINES DO NOT EXIST ON THE EC AT THE | | | LINK ABOVE. PLEASE COMPLETE THE EC ON THE CORRECT FORM | | | AND SEND VIA EMAIL TO [email protected]; INCLUDE THE | | | PERMIT NUMBER IN THE SUBJECT LINE. | | | | | | 2. A9 C DOES NOT STATE NET AREA OF FLOOD OPENINGS, A9B | | | DOES NOT STATE THE NUMBER OF FLOOD OPENINGS. THE PLANS | | | SHOW LOUVERS WITH CALCULATIONS. PLEASE COMPLETE THESE | | | TWO FIELDS; THIS CANNOT BE NA AS VENTS ARE REQUIRED | | | (GARAGE FLOOR DOES NOT MEET 2' FREEBOARD REQUIREMENT). | | | | | | |
|