Plan Review Notes
Plan Review Notes For Permit 19051263
Permit Number 19051263
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2019-06-17 13:13:17BUILDING PLAN REVIEW - NFIP
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 FINISH FLOOR ELEVATION OF 8'1" NAVD 88 - OK. NO
 RESPONSE NECESSARY
  
 1. NFIP - PROPERTY IS LOCATED IN FLOOD ZONE AE WITH A
 BASE FLOOD ELEVATION (BFE) OF 6'0" NAVD88. AMENDMENTS
 TO THE CITY OF WEST PALM BEACH, ORDINANCE NO. 4729-17
 REQUIRES 2 FEET OF FREE BOARD. DESIGN FLOOD ELEVATION
 (DFE) WILL BE AT 8'0" NAVD88.
 AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT
 AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE
 MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD
 HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM
 BEACH, FL.
 ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON
 NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM
 BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT FREEBOARD
 ABOVE THE (BFE).
  
 ELEVATION CERTIFICATES REQUIRED.
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION. MINIMUM FINISH
 FLOOR ELEVATION SHALL BE 8'0" NAVD88.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 8 FEET NAVD.
 AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED
 FLOOR ELEVATION IS REQUIRED.
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 THIS EC MAY BE SUBMITTED FOR REVIEW PRIOR TO BUILDING
 FINAL.
  
 2. FLOOD VENTS REQUIRED IN ATTACHED GARAGE.
 G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION.
  
 FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION
 SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO
 THE FOLLOWING:
  
 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY
 WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS
 TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF
 FLOODWATERS.
  
  
  