| 2019-06-17 13:13:17 | BUILDING PLAN REVIEW - NFIP |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | FINISH FLOOR ELEVATION OF 8'1" NAVD 88 - OK. NO |
| | RESPONSE NECESSARY |
| | |
| | 1. NFIP - PROPERTY IS LOCATED IN FLOOD ZONE AE WITH A |
| | BASE FLOOD ELEVATION (BFE) OF 6'0" NAVD88. AMENDMENTS |
| | TO THE CITY OF WEST PALM BEACH, ORDINANCE NO. 4729-17 |
| | REQUIRES 2 FEET OF FREE BOARD. DESIGN FLOOD ELEVATION |
| | (DFE) WILL BE AT 8'0" NAVD88. |
| | AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT |
| | AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE |
| | MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD |
| | HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM |
| | BEACH, FL. |
| | ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON |
| | NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM |
| | BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT FREEBOARD |
| | ABOVE THE (BFE). |
| | |
| | ELEVATION CERTIFICATES REQUIRED. |
| | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS |
| | REQUIRED AT TIME OF PERMIT APPLICATION. MINIMUM FINISH |
| | FLOOR ELEVATION SHALL BE 8'0" NAVD88. |
| | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS |
| | SITE ARE REQUIRED TO BE AT OR ABOVE 8 FEET NAVD. |
| | AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED |
| | FLOOR ELEVATION IS REQUIRED. |
| | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| | THIS EC MAY BE SUBMITTED FOR REVIEW PRIOR TO BUILDING |
| | FINAL. |
| | |
| | 2. FLOOD VENTS REQUIRED IN ATTACHED GARAGE. |
| | G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION. |
| | |
| | FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION |
| | SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO |
| | THE FOLLOWING: |
| | |
| | 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY |
| | WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS |
| | TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF |
| | FLOODWATERS. |
| | |
| | |
| | |