| Plan Review Notes For Permit 19051192 |
| Permit Number |
19051192 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-24 09:59:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SITE PLAN DOES NOT INDICATE THE TYPE OF ROAD | | | BLOCKS/BARRICADES THAT WILL BE USED. | | | | | | THE BARRICADES MUST BE MOVEABLE FORE EMERGENCY | | | APPARATUS AND RESPONDER ACCRESS. | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF FIRE LANES ALONG | | | CLEMATIS THAT EMERGENCY APPARATUS CAN USE IN THE EVENT | | | OF AN INCIDENT | | | | | | THERE MUST BE A MINIMUM OF HALF THE ROADWAY WIDTH FOR | | | TRAVEL, ANYTHING THAT OBSTRUCTS THE TRAVEL ATH MUSBT BE | | | IMMEDIATELY MOVEABLE. | | | | | | | | | 3) PLEASE PROVIDE DETAILS ON THE RESUBMITTAL. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|