| 2019-06-07 08:45:39 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19051178 (BLDG 15) |
| | REVIEWED: JUNE 7, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | |
| | 1) 107.5.3 FBC[AMENDED] MEAN ROOF HEIGHT (MRH) |
| | - PLEASE ADJUST WIND DESIGN DATA ON SHEET A2 FOR MRH. |
| | THIS IS THE HEIGHT OF FLAT ROOF DECK OR MEDIAN FOR |
| | PITCHED ROOF. |
| | |
| | 2) 1603.1.4 FBC[B] WIND DESIGN DATA. WIND-BORNE DEBRIS |
| | REGION. |
| | - WIND DESIGN DATA ON SHEET A2 STATES 180 MPH. YOU CAN |
| | USE 170 M.P.H. AS V ULT AND 132 ASD. YOU CAN ALWAYS |
| | BUILD TO HIGHER STANDARD, BUT FOR CAT II BUILDINGS WE |
| | USE 170. |
| | |
| | 3) 606.1 FBC EXIST]GENERAL. STRUCTURAL REPAIRS SHALL BE |
| | IN COMPLIANCE WITH THIS SECTION AND SECTION 601.2. |
| | REGARDLESS OF THE EXTENT OF STRUCTURAL OR NONSTRUCTURAL |
| | DAMAGE, DANGEROUS CONDITIONS SHALL BE ELIMINATED. |
| | REGARDLESS OF THE SCOPE OF REPAIR, NEW STRUCTURAL |
| | MEMBERS AND CONNECTIONS USED FOR REPAIR OR |
| | REHABILITATION SHALL COMPLY WITH THE DETAILING |
| | PROVISIONS OF THE FLORIDA BUILDING CODE, BUILDING FOR |
| | NEW BUILDINGS OF SIMILAR STRUCTURE, PURPOSE AND |
| | LOCATION. |
| | - PLEASE PROVIDE CONNECTION DETIAL FOR NEW RAIL TO |
| | EXISTING 6X8 POSTS. ALSO, PROVIDE DETAIL OF FLOOR |
| | JOISTS IF THEY NEED REPLACEMENT. HOW DOES IT ATTACH TO |
| | EXISTING WALL? |
| | |
| | NOTES: |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |
| | |