| 2019-06-11 08:22:48 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. WIND LOAD DESIGN CRITERIA DETAILED IN NOTE 10 AND 11 |
| | ON SHEET E3.01 DOES NOT MATCH THE WIND LOAD DESIGN |
| | REQUIRED FOR THIS AREA. ADDITIONALLY, THE EXCEPTION |
| | NUMBER 7 MENTIONED FOR 1609.1.1 IN NOTE 10 IS FOR |
| | SCREEN ENCLOSURES. PROVIDE CORRECTION. FBC 1609.3, |
| | 1609.1.1 |
| | 2. SHEET E3.00 HAS A BLOCK NOTE, AND NOTE 5, THAT |
| | STATES A WIND LOADING CALCULATION, WHICH IS |
| | SIGNED/SEALED BY A STRUCTURAL ENGINEER, SHALL BE |
| | PROVIDED TO CONFIRM THE PROPOSED INSTALLATION SHALL |
| | MEET THE FBC WIND LOAD REQUIREMENTS. THIS HAS NOT BEEN |
| | PROVIDED. PROVIDE CORRECTION. WPB FBC 107.2.1; FBC |
| | 1609.1 |
| | 3. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH FBC |
| | ENERGY CONSERVATION. FBC EC C405.6.3 |
| | 4. SHEET E2.01 SHOWS DETAILS FOR A RECEPTACLE POLE. |
| | WHERE WILL THESE BE INSTALLED? ARE THEY IN ADDITION TO |
| | THE GFCI RECEPTACLES THAT WILL BE INSTALLED ON LIGHT |
| | POLES? FOR GFCI RECEPTACLES, WHETHER ON LIGHT POLES OR |
| | A SEPARATE POLE, WILL THESE BE CONTROLLED THROUGH THE |
| | LIGHTING CONTACTOR CONTROLLED BY PHOTOCELL, OR POWERED |
| | CONTINUALLY?THE PLAN DOES NOT SPECIFY CONTROL FOR |
| | RECEPTACLES. PROVIDE CLARIFICATION. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |