| Plan Review Notes For Permit 19051134 |
| Permit Number |
19051134 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-08 15:56:15 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | GROUNDING ELECTRODES TO BE COMMON RUN A JUMPER FROM | | | GENERATOR GE TO SERVICE GE. 250.58 | | | | | | YOU HAVE THREE (3) #1S FROM TRANFERSWITCH TO TAP BOX | | | AND THEN FOUR (4) #4S TO 150A DISCONNECTS, MISSING AND | | | EQUIPMENT GROUND FROM TRANSFERSWITCH. | | | | | | NOTE AT TOP OF DRAWING ABOUT NEUTRAL ???? |
|