2019-07-08 15:56:15FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 GROUNDING ELECTRODES TO BE COMMON RUN A JUMPER FROM
 GENERATOR GE TO SERVICE GE. 250.58
  
 YOU HAVE THREE (3) #1S FROM TRANFERSWITCH TO TAP BOX
 AND THEN FOUR (4) #4S TO 150A DISCONNECTS, MISSING AND
 EQUIPMENT GROUND FROM TRANSFERSWITCH.
  
 NOTE AT TOP OF DRAWING ABOUT NEUTRAL ????