| Plan Review Notes For Permit 19051126 |
| Permit Number |
19051126 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-23 19:11:17 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | SUBMITTAL DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PAVER ATTACHMENT ANALYSIS IS NOT SIGNED AND | | | SEALED BY THE FLORIDA ENGINEER, MARK A. DE STEFANO, PE | | | AS REQUIRED BY FL 471 AND FAC 61G15-23.003. | | | | | | 2) THE ENGINEER'S ANALYSIS REQUIRES THE PAVERS AND | | | PEDESTALS TO BE ADHERED WITH CARLISLE CCW-201 SEALANT | | | WITH A TENSILE STRENGTH OF 200 PSI OR APPROVED EQUAL. | | | BECAUSE YOU ARE USING A DIFFERENT PRODUCT, GAF FLEXSEAL | | | SEALANT, THE ENGINEER IS REQUIRED TO APPROVE IT. FBC | | | 107.2 | | | | | | |
|