| Plan Review Notes For Permit 19051117 |
| Permit Number |
19051117 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-06-13 11:21:41 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) | | | 805-6724 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. GENERAL LIMITATION #7 IS SPECIFICALLY REFERRED TO IN | | | THIS NOA. PERIMETER AND CORNER AREAS SHALL COMPLY WITH | | | THE ENHANCED UPLIFT PRESSURE REQUIREMENTS OF THESE | | | AREAS. FASTENER DENSITIES SHALL BE INCREASED FOR BOTH | | | INSULATION AND BASE SHEET AS CALCULATED IN COMPLIANCE | | | WITH ROOFING APPLICATION STANDARD RAS 117. CALCULATIONS | | | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR | | | REGISTERED ROOF CONSULTANT. | | | |
|