2019-06-13 11:21:41JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 1ST REVIEW FBC 2017 EXISTING BUILDING
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. GENERAL LIMITATION #7 IS SPECIFICALLY REFERRED TO IN
 THIS NOA. PERIMETER AND CORNER AREAS SHALL COMPLY WITH
 THE ENHANCED UPLIFT PRESSURE REQUIREMENTS OF THESE
 AREAS. FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION AND BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARD RAS 117. CALCULATIONS
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR
 REGISTERED ROOF CONSULTANT.
  