| Plan Review Notes For Permit 19051097 |
| Permit Number |
19051097 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-08-06 14:31:21 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) | | | 805-6724 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. AN ENGINEERING EVALUATION AND ANALYSIS THAT | | | ESTABLISHES THE STRUCTURAL ADEQUACY OF THE ALTERED | | | STRUCTURE SHALL BE PREPARED BY A REGISTERED DESIGN | | | PROFESSIONAL AND SUBMITTED TO THE CODE OFFICIAL. AS PER | | | 907.4.1 AND 907.4.2 FBC-EB. PROVIDE TWO SETS. | | | 2. FBC B 107.2.1. PLEASE CLARIFY; CONNECTION DETAIL | | | PAGE S-1 SHOWS 2?X 6? WOOD BEAMS, DECK FRAMING PLAN | | | PAGE S-2 SHOWS 2?X 10? WOOD BEAMS AT PERIMETER. VERIFY | | | JOIST HANGERS TO BE USED. | | | 3. FBC B 107.2.1. PLEASE CLARIFY; ELEVATION DETAILS | | | PAGE S-1. WEST ELEVATION DETAIL SHOULD BE NORTH | | | ELEVATION AND EAST ELEVATION DETAIL SHOULD BE WEST | | | ELEVATION. | | | |
|