| 2019-06-10 15:35:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET S 1 - THE PROPOSED PROJECT INDICATED A DOOR; |
| | HOWEVER, THE SIZE OF THE DOOR IS NOT PROVIDED. |
| | |
| | THIS DOOR SHALL BE WIDE ENOUGH TO MEET THE MINIMUM |
| | WIDTH FOR AN EXIT. |
| | |
| | PER NFPA 101, CH 7 |
| | |
| | 7.3.4.1.2 IN EXISTING BUILDINGS, THE WIDTH OF EXIT |
| | ACCESS SHALL BE |
| | PERMITTED TO BE NOT LESS THAN 28 IN. |
| | |
| | PLEASE PROVIDE THE DOOR WIDTH. |
| | |
| | |
| | |
| | 2) SHEET S 1 - THERE IS NO DOOR HARDWARE INDICATED FOR |
| | THE DOOR. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | |
| | PLEASE PROVIDE DOOR HARDWARE DETAILS. |
| | |
| | |
| | 3) SHEET S 1 - THERE ARE NO ROOF DECKING MANUFACTORES |
| | SPECIFICATION SHEETS. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | 4) SHEET S 1 - IT APPEARS ON THE EAST ELEVATION THERE |
| | IS A STEP DOWN IN THE MIDDLE OF THE DECKING. |
| | |
| | THE DECK FLOOR PLAN DOES NOT SHOW IT. |
| | |
| | PLEASE CLARIFY AND PROVIDE THE STEP DIMENSION COMPLIANT |
| | WITH THE CODE. |
| | |
| | |
| | 5) SHEET S 1 - THERE IS NO INDICATION OF THE TRAVEL |
| | DISTANCE TO THE EXIT DISCHARGE GOING THROUGH THE DOOR |
| | TO THE INTERIOR OF THE BUILDING. |
| | |
| | PLEASE PROVIDE THE EXISTING EXIT PATH AND TRAVEL |
| | DISTANCE THROUGH THE INTERIOR OF THE BUILDING TO THE |
| | EXIT DISCHARGE. |
| | |
| | PER NFPA 101, CH 12 |
| | |
| | 12.2.6 TRAVEL DISTANCE TO EXITS. |
| | 12.2.6.1 TRAVEL DISTANCE SHALL BE MEASURED IN |
| | ACCORDANCE WITH |
| | SECTION 7.6. |
| | |
| | PLEASE SHOW FLOOR PLAN AND PROVIDE DETAILS |
| | |
| | |
| | |
| | 6) THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |