2019-06-06 16:07:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
 1. PER FBC ACC 604.8.1, DOORS SHALL BE LOCATED IN THE
 FRONT PARTITION OR IN THE SIDE WALL OR PARTITION
 FARTHEST FROM THE WATER CLOSET. WHERE LOCATED IN THE
 FRONT PARTITION, THE DOOR OPENING SHALL BE 4 INCHES
 (100 MM) MAXIMUM FROM THE SIDE WALL OR PARTITION
 FARTHEST FROM THE WATER CLOSET. WHERE LOCATED IN THE
 SIDE WALL OR PARTITION, THE DOOR OPENING SHALL BE 4
 INCHES (100 MM) MAXIMUM FROM THE FRONT PARTITION. THE
 DOOR SHALL BE SELF-CLOSING. A DOOR PULL COMPLYING WITH
 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR NEAR
 THE LATCH. TOILET COMPARTMENT DOORS SHALL NOT SWING
 INTO THE MINIMUM REQUIRED COMPARTMENT AREA.
 2. PER WPB FBC 107.2.1, SHOW CLEAR FLOOR SPACE FOR
 LAVATORIES AS REQUIRED BY WITH FBC ACC 305 AND 306.
 3. PER FBC ACC 603.2.3, DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY
 FIXTURE.THIS IS APPLICABLE TO THE LAVATORIES.
 4. PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING DETAILS:
 A. MIRROR ELEVATION PER FBC ACC 603.3
 B. KNEE AND TOE CLEARANCE FOR LAVATORIES; REFER TO FBC
 ACC 306 FIGURES 306.2 AND 306.3.
 C. FLUSH CONTROL SHALL BE LOCATED ON THE OPEN SIDE OF
 THE WATER CLOSET PER FBC ACC 604.6.
 D. GRAB BARS SHALL BE MINIMUM 33?/MAXIMUM 36? TO THE
 TOP OF THE GRIPPING SURFACE PER FBC ACC 609.4
 E. CENTER LINE OF WATER CLOSET TO BE 16?MINIMUM/18?
 MAXIMUM FROM SIDE WALL PER FBC ACC 604.2.
 F. SEAT HEIGHT OF WATER CLOSET FROM FINISH FLOOR TO TOP
 OF SEAT SHALL BE 17? MINIMUM/19? MAXIMUM PER FBC ACC
 604.4.
 G. PER FBC ACC 604.7, TOILET DISPENSER SHALL BE 7? TO
 9? FROM FRONT OF WATER CLOSET TO CENTER OF DISPENSER.
 THE OUTLET SHALL BE 15? MINIMUM/48? MAXIMUM ABOVE THE
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19051081 909 FERN ST
  