Plan Review Notes
Plan Review Notes For Permit 19051075
Permit Number 19051075
Review Stop G
Sequence Number 1
Notes
Date Text
2019-05-30 14:43:521ST GAS REVIEW**DENIED**
  
 1) CPC CONTRACTOR IS NOT PERMITTED UNDER F.S 489 TO
 PERFORM GAS WORK. A PLUMBING CONTRACTOR OR L.P 408E
 MUST APPLY FOR PERMIT
  
 2) NO PLANS HAVE BEEN SUBMITTED. PROVIDE GAS ISOMETRIC
 DRAWING SHOWING PIPE SIZE, PIPE MATERIAL, AND PROVIDE
 SIZING CHARHTS THAT SYSTEM IS BASED OFF OF. IF AN
 EXISTING SYSTEM YOU MUST INCLUDE THE BTU LOAD OF ALL
 EXISTING APL ON SYSTEM. FBC 107.3.5
  
 3) PLANS SHALL BE SIGNED AND SEALED. F.S 471
  
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  